3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-63
3.1.5.4 Product Profile and Outline
L+
L-
SLD
C
H
1
L+
L-
C
H
2
EL
C-
T
C
0
4
A
NNN
A/D
ERROR
POWER
25.20
60.00
1
2
3
4
6
10
9
5
7
8
11
13
90.00
3.00
12
14
L+
L-
SLD
C
H
3
L+
L-
SLD
C
H
4
3.00
SLD
Units: mm
1. Status indicator (Power, ERROR and A/D)
2. Model Name
3. Extension unit clip
4. I/O terminals
5. DIN rail clip
6. Mounting hole of the extension unit
7. Nameplate
8. Extension hook
9. DIN rail mounting slot (35mm)
10. Extension port
11. RS-485 Communication port
12.
2 pin removable terminal (standard
accessory)
13. DC power input
14. Power input cable (standard accessory)
3.1.5.5 Installation and Wiring
Installation of the DIN rail
1. The ELC may be secured to a cabinet by using 35mm in height and 7.5mm in
depth DIN rail. When mounting the ELC to 35mm DIN rail, be sure to use the
retaining clip to stop any side-to-side movement of the ELC and reduce the
chance of wires coming loose. The retaining clip is at the bottom of the ELC. To
secure the ELC to DIN rail, pull down the clip, place it onto the rail and push it up
to lock it in place. To remove the ELC, pull the retaining clip down with a flat
screwdriver and remove the ELC from DIN rail.
2.
Install the ELC in an enclosure with sufficient space around it to allow heat dissipation, as
shown in the figure below.