E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-164
Mode 5 (H’0005): E-type (-150°C ~ 980°C).
Mode 6 (H’0006): N-type (-150°C ~ 1,280°C).
Mode 7 (H’0007): -80mV~+80mV
Mode-1 (H’FFFF): Channel 1 unavailable
C R # 7 :
Configure Temperature units
Select the temperature units for average and present temperatures. (Celsius °C / Fahrenheit
°F). Default = H’0000.
Mode 0 (H’0000): Celsius °C.
Mode 1 (H’0001): Fahrenheit °F.
C R # 8 , 9 , 1 0 , 11 :
CH1 ~ CH4 number of samples
1. The number of samples for the average temperature values for CH1 ~ CH4.
2. Range for ELCM-TC04ANNN: K1 ~ K100. Default = K10. If the configured value exceeds
K100, the value will be set to K100; if the configured value is less than K1, the value will
be set to K1
C R # 1 2 , 1 3 , 1 4 , 1 5 :
Average temperatures measured at CH1 ~ CH4
The average temperature measured at CH1 ~ CH4 is calculated based on the number of
samples set in CR#8 ~ CR#11. Temperature units: set in CR#7. For example, if the number of
samples is set to K10, the contents of CR#12 ~ CR#15 will be the average of the most recent
10 temperature signals received in CH1 ~ CH4
C R # 2 0 , 2 1 , 2 2 , 2 3 :
Present temperature measured at CH1 ~ CH4
The present temperatures at CH1 ~ CH4. Temperature units: set in CR#7.
C R # 2 8 , 2 9 , 3 0 , 3 1 :
Adjusted Offset value for CH1 ~ CH4
1. Set the adjusted Offset value for CH1 ~ CH4.
2. Range:
K-400~K400
3. Default setting = K0.
z
Mode 0 ~ Mode 6: 1
SCALE
= 0.1°
Equation:
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛
+
°
°
=
Offset
X
Y
)
(
1
.
0
)
(
Y=Digital output, X= Measured input