E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-120
C R # 4 2 :
Function: Return to default settings. Default = H0000
Description
bit0
b0=0, no action on CH1; b0=1, set CH1
to default setting
bit1
b1=0, no action on CH2; b1=1, set CH2 to default setting
bit2
b2=0, no action on CH3; b2=1, set CH3 to default setting
bit3
b3=0, no action on CH4; b3=1, set CH4 to default setting
bit4
B4=0, no action on CH5; b4=1, set CH5 to default setting
bit5
B5=0, no action on CH6; b5=1, set CH6 to default setting
bit6 ~ bit15
Reserved
Note: Set the appropriate bit to 1 and the corresponding channel will be returned to default
settings. When complete, the value will be set to 0. If CR#40 (Prohibit Configuration changes)
is enabled, setting defaults will be invalid, and all configuration values will remain unchanged.
Error Code bit 12 of CR#43 will be set to 1.
Affected Parameters
CR#2 ~ CR#5
Input mode setting of CH1 ~ CH4
CR#6 ~ CR#7
Output mode setting at CH5 ~ CH6
CR#8 ~ CR#11
Sampling range of CH1 ~ CH4
CR#28 ~ CR#33
Adjusted Offset value at CH1 ~ CH6
CR#34 ~ CR#39
Adjusted Gain value at CH1 ~ CH6
CR#100
Function: Enable/Disable limit detection
CR#102~CR#107 Set value of CH1~CH6 upper bound
CR#108~CR#113 Set value of CH1~CH6 lower bound
CR#114~CR#115 Output update time of CH5 ~ CH6
CR#118
LV output mode setting
C R # 4 3 :
Error status. Default=H’0000
CR#43: error status value. See the table below:
Description
bit0
K1 (H’1)
Power Supply error
bit1
K2 (H’2)
Hardware error
bit2
K4 (H’4)
Upper / lower limit error
bit3
K8 (H’8)
CH1 Conversion error
bit4
K16 (H’10)
CH2 Conversion error
bit5
K32 (H’20)
CH3 Conversion error
bit6
K64 (H’40)
CH4 Conversion error