6.1.2.4 Installation and Wiring
Installation of the DIN rail
1. The ELC can be secured to a cabinet by using the DIN rail that is 35mm high with a depth of
7.5mm.When mounting the ELC on the DIN rail, be sure to use the end bracket to stop any
side-to-side motion of the ELC, thus to reduce the chance of the wires being pulled loose.
At the bottom of the ELC is a small retaining clip. To secure the ELC to the DIN rail, place it
onto the rail and gently push up the clip.
2. When installing the ELC, make sure that it is installed in an enclosure with sufficient space
to its surroundings so as to allow heat dissipation. As shown on the below.
Direct Mounting:
Please use M4 screw according to the dimension of the product.
6.1.2.5 Configuration
Connection of ELC-485APTR and AC Motor Drive (please see AC motor drive user manual for detail
information)
MVX 9000
RS-485 Network
Fig.2: ELC controller connection with MVX9000
Compact Installation reference:
See Fig. 3a in lower left, when ELC-485APTR is separated from mounting plate, it can be used
as the last extension module with its RS-485 port connecting to ELC controller’s (see Fig. 3b for
illustration). This connection is feasible for ELC controller to connect AC Motor Drive within 5
meters.