3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-7
ELC-AN04ANNN
EXPLANATION
bit
CR
No
Param.
Comm.
Add.
Latched
Register Name
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
#14 H’400E X
R
Present value of CH3
input signal
#15 H’400F X
R
Present value of CH4
input signal
Present values of CH3~CH4 input signals
#18 H’4012 O R/W
To adjust OFFSET
value of CH1
#19 H’4013 O R/W
To adjust OFFSET
value of CH2
#20 H’4014 O R/W
To adjust OFFSET
value of CH3
#21 H’4015 O R/W
To adjust OFFSET
value of CH4
Offset for CH1~CH4. Factory setting is K0..
Voltage input: range is K-4,000 ~K4,000
Current input: range is K-4,000 ~K4,000
#24 H’4018 O R/W
To adjust GAIN value
of CH1
#25 H’4019 O R/W
To adjust GAIN value
of CH2
#26 H’401A O R/W
To adjust GAIN value
of CH3
#27 H’401B O R/W
To adjust GAIN value
of CH4
GAIN of CH1~CH4. Factory setting is K4,000.
Voltage input: range is K-3,200 ~K16,000.
Current input: range is K-3,200 ~K10,400.
#30 H’401E X
R Error status
Error code. Please refer to fault code chart for details.
#31 H’401F O R/W
Communication
address setting
RS-485 communication address. Range is 01~255 and
factory setting is K1
#32 H’4020 O R/W
Communication baud
rate setting
Used to set communication baud rate (4,800, 9,600,
19,200, 38,400, 57,600, 115,200bps). Communication
format: ASCII mode is 7Bit, even parity, 1 stop bit (7, E,
1). Communication format of RTU mode is 8Bit, even
parity, 1 stop bit (8, E, 1).
b0: 4,800 bps (bit/sec).
b1: 9,600 bps (bit/sec). (factory setting)
b2: 19,200 bps (bit/sec).
b3: 38,400 bps (bit/sec).
b4: 57,600 bps (bit/sec).
b5: 115,200 bps (bit/sec).
b6 ~ b13: reserved.
b14: exchange low and high byte of CRC check code
(only for RTU mode)
b15: ASCII / RTU mode selection