E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-170
Output Y0
t=1000ms
T=2000ms
C R # 1 3 4 , 1 5 4 , 1 7 4 , 1 9 4 :
Output volume
Formula for output volume:
Output Volume = (Output Upper Limit – Output Lower Limit) × Output % + Output Lower
Limit
Example:
Control with current 4 ~ 20mA (0 ~ 32,000)
Output upper limit: 32,000
Output lower limit: 0
32000
(100% )
16000
(50%)
0 (0%)
4mA
12mA
20mA
Output volume
Output
current
C R # 1 3 5 , 1 5 5 , 1 7 5 , 1 9 5 :
PID_RUN/STOP
1. To apply the auto-tuning function, enable the auto-tuning function before changing the
PID function to RUN. When auto-tuning is completed, CR#136, 156, 176, 196 will
be cleared to 0, and the value for K
P
/ K
I
/ K
D
will be stored into the corresponding
CRs.
2. PID_RUN/STOP, K0: STOP, K1: RUN. Default = K0.
C R # 1 3 6 , 1 5 6 , 1 7 6 , 1 9 6 :
Auto-tuning
1. To apply the auto-tuning function, set the auto-tuning CR to K1 to enable the auto-tuning
function before changing PID function to RUN. When auto-tuning is complete, CR#136,
156, 176, 196 will be cleared to 0, and the value of K
P
/ K
I
/ K
D
will be stored
into the corresponding CRs.
2. Auto-tuning, K0: Disabled, K1: Auto-tuning. Default = K0.
Notes:
1. Set
K
P
, K
I
, and K
D
to “0" to disable the PID function. If you want to use proportional control
only, set K
I
and K
D
to “0”.