E L C O p e r a t i o n M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003006E
1-142
CR#
Attrib.
Register content
Description
#7
O R/W Temperature unit setting
Select the temperature units (Celsius °C / Fahrenheit
°F). Default = H0(°C)
#8
O R/W CH1 number of samples
#9
O R/W CH2 number of samples
#10 O R/W CH3 number of samples
#11 O R/W CH4 number of samples
Set number of samples for CH1 ~ CH4
Range = K1 ~ K100
Default = K10
#12 X R
Average temperature
measured at CH1
#13 X R
Average temperature
measured at CH2
#14 X R
Average temperature
measured at CH3
#15 X R
Average temperature
measured at CH4
Average temperature measured at CH1 ~ CH4.
Temperature units: set in CR#7
Average temperatures are based on the number of
samples in CR#8-11.
#20 X R
Present temperature measured
at CH1
#21 X R
Present temperature measured
at CH2
#22 X R
Present temperature measured
at CH3
#23 X R
Present temperature measured
at CH4
Present temperature measured at CH1 ~ CH4.
Temperature units: set in CR#7
#28 O R/W Adjusted Offset value of CH1
#29 O R/W Adjusted Offset value of CH2
#30 O R/W Adjusted Offset value of CH3
#31 O R/W Adjusted Offset value of CH4
Set the adjusted Offset value of Ch1 ~ Ch4. Default
= K0
Range: K-400 ~ K400
Temperature unit: set in CR#7
Definition of Offset at Ch1 ~ Ch4 in
ELCM-PT04ANNN:
Deviation digital value from the target value.
#40 O R/W
Function: Set value changing
prohibited
Prohibit configuration changes for CH1 ~ CH4
#41 X R/W
Function: Save all the set
values
Save all configuration values, Default =H’0000
#42 X R/W
Function: Return to default
setting
Set all values to default setting, Default = H’0000
#43 X R Error
status
Register for storing all error status. See the table of
error status for more information.
#100 O R/W
Function: Enable/Disable limit
detection
Enable/Disable the upper and lower limit detection
function. Default= H’0000.
#101 X R/W Upper and lower limit status
Display the upper and lower limit value, Default
=H’0000
#102 O R/W Set value for CH1 upper limit
#103 O R/W Set value for CH2 upper limit
#104 O R/W Set value forCH3 upper limit
#105 O R/W Set value for CH4 upper limit
Set value of CH1~CH4 upper limit. Default =
K32000.
#108 O R/W Set value for CH1 lower limit
#109 O R/W Set value for CH2 lower limit
#110 O R/W Set value for CH3 lower limit
#111 O R/W Set value for CH4 lower limit
Set value of CH1~CH4 lower limit. Default =
K-32000.