3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-57
ELC- PT04ANNN
EXPLANATION
bit
CR
No
Param.
Comm.
Add.
Latched
Register Name
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
O means latched. X means not latched. (available when using RS-485 communication, not available
when connected to MPU)
R means can read data by using FROM command or RS-485.
W means can write data by using TO command or RS-485.
Description of the CRs
C R # 0 :
Module Type
1. ELC- PT04ANNN model code = H’008A.
2. Read the module code in the program to verify the correct extension module.
C R # 2 , 3 , 4 , 5 :
Number of samples for the average values for CH1 ~ CH4
1. The number of samples used to determine the average temperature values for CH1 ~
CH4.
2. Range for ELC- PT04ANNN: K1 ~ K100. Default = K10.
C R # 6 , 7 , 8 , 9 :
Average Celsius temperature measured at CH1 ~ CH4
1. The average Celsius temperature measured at CH1 ~ CH4 obtained from the number of
samples in CR#2 ~ CR#5. Unit: 0.1°C.
2. For example, if the number of samples is set to 10, the contents in CR#6 ~ CR#9 will be
the average of the most recent 10 temperature values in Celsius at CH1 ~ CH4.
C R # 1 2 , 1 3 , 1 4 , 1 5 :
Average Fahrenheit temperature measured at CH1 ~ CH4
1. The average Fahrenheit temperature measured at CH1 ~ CH4 obtained from the number
of samples in CR#2 ~ CR#5. Unit: 0.1°F.
2. For example, if the number of samples is set to 10, the contents in CR#12 ~ CR#15 will
be the average of the most recent 10 temperature values in Fahrenheit at CH1 ~ CH4.
C R # 1 8 , 1 9 , 2 0 , 2 1 :
Present Celsius temperature measured at CH1 ~ CH4
The present temperature in Celsius at CH1 ~ CH4. Unit: 0.1°C.
C R # 2 4 , 2 5 , 2 6 , 2 7 :
Present Fahrenheit temperature measured at CH1 ~ CH4
The present temperature in Fahrenheit at CH1 ~ CH4. Unit: 0.1°F.