3. AIAO Units
MN05003006E F or more information visit:
w w w. e a t o n . c o m
1-79
Parameters prohibited or allowed by b0~b3 above
CR#2 ~ CR#5
Input mode setting for CH1 ~ CH4
CR#8 ~ CR#11
Number of samples for CH1 ~ CH4
CR#28 ~ CR#31
Adjusted Offset values for CH1 ~ CH4
CR#34 ~ CR#37
Adjusted Gain values for CH1 ~ CH4
CR#42
Return to default settings
CR#100
Function: Enable/Disable limit detection
CR#102~CR#105
Set value of CH1~CH4 upper limit
CR#108~CR#111 Set
value
of CH1~CH4 lower limit
C R # 4 1 :
Function: Save all configuration values. Default=H0000
Save configuration settings. Save all the configuration values to internal flash memory. When
saving is completed, CR#41 will be set to H’FFFF.
Set value
Function
H0 No
action
HFFFF Saving
complete
H5678 Saving
enabled.
Note: Default setting = H0. When set value = H’5678, saving will be enabled, and CR#41 will
be set to H’FFFF when saving is complete.
C R # 4 2 :
Function: Return to factory default settings. Default=H0000
Description
bit0
b0=0, no action on CH1; b0=1, set CH1
to default settings
bit1
b1=0, no action on CH2; b1=1, set CH2 to default settings
bit2
b2=0, no action on CH3; b2=1, set CH3 to default settings
bit3
b3=0, no action on CH4; b3=1, set CH4 to default settings
bit4 ~ bit15
Reserved
Note: Set designated bit to 1 and the corresponding channel will be returned to default
settings. When this process is complete, the value will be set to 0 again. If CR#40 is enabled,
this operation will not execute and. Error Code bit 12 of CR#43 will be set to 1.
Relative Parameters
CR#2 ~ CR#5
Input mode setting of CH1 ~ CH4
CR#8 ~ CR#11
Sampling range of CH1 ~ CH4
CR#28 ~ CR#31
Adjusted Offset value of CH1 ~ CH4
CR#34 ~ CR#37
Adjusted Gain value of CH1 ~ CH4
CR#100
Function: Enable/Disable limit detection