Operation using HART communicator
Azbil Corporation
7-18
Model MTG11A/18A, MTG11B/18B, MTG14C
Electrode status output mode
2.
Once the display as shown Figure 7-28 appears, move the arrow key up or
down to select a sensitivity. After marking a selection, press F4 (ENTER).
OFF, HIGH, MID, LOW, LL, or LLL can be selected. If F3 (ESC) is pressed
here, the selection is canceled and the display returns to the Noise immunity
menu.
3.
After returning to the Noise immunity menu, press F2 (SEND). The changed setting is
sent to the transmitter. The HART communicator mark appears on the upper side while
HART is communicating with the device. Once communication is completed, the HART
mark disappears.
4.
To select an appropriate sensitivity level, refer to the flow chart on page 5-28.
1.
From online menu,
Select:
1. Device setup
4. Detailed setup
3. Noise immunity
8. Electrode status output mode
Figure 7-29 is then displayed.
Figure 7-29
2.
Once the display as shown
Figure 7-29
appears, move the arrow key up or down to
select an Electrode status output mode. After marking a selection, press F4 (ENTER).
OFF, ZERO, or HOLD can be selected. If F3 (ESC) is pressed here, the selection is
canceled and the display returns to the Noise immunity menu.
3.
After returning to the Noise immunity menu, press F2 (SEND). The changed setting is
sent to the transmitter. The HART communicator mark appears on the upper side while
HART is communicating with the device. Once communication is completed, the HART
mark disappears.
CM2-MTG300-2001.book 18 ページ 2015年9月29日 火曜日 午前10時14分
Summary of Contents for MagneW Neo PLUS
Page 16: ...List of Figures Tables CM2 MTG300 2001 book 4...
Page 92: ...MEMO CM2 MTG300 2001 book 38...
Page 106: ...MEMO CM2 MTG300 2001 book 4...
Page 266: ...MEMO CM2 MTG300 2001 book 82...
Page 312: ...MEMO CM2 MTG300 2001 book 46...
Page 336: ...MEMO CM2 MTG300 2001 book 22...
Page 338: ...CM2 MTG300 2001 book 2...