Maintenance and troubleshooting
Model MTG11A/18A, MTG11B/18B, MTG14C
8-7
Troubles at startup
Troubleshooting
When a problem occurs at start-up, perform the following procedures. If the problem
remains, it is possible that the device has been damaged. Contact an Azbil Copr.
representative.
Trouble
Check point and troubleshooting
No indication on display
panel when powered on.
• Check the specifications of the power source.
• Check the wiring.
• Check if the ambient temperature is not under -4°F
(-20°C).
No output when powered
on.
• Check the signal line for correct connection.
Communication failure.
• Check the signal line for correct connection. A load
resistance of 250
Ω
or more is required (SFC).
• Check the communicator for correct connection.
(SFC has polarity.)
• SFC of Version 7.0 or later is used. Operation is
impossible with a lower version.
• Is model MTG DD (device description) down-
loaded on the HART Communicator? The DD for
the model MTG should be downloaded from HCF
DD Library Host DD Distribution (HCF-KIT-III)
Release 2002 Number 3 or later.
No pulse output
• Check the counter type, input specifications and
contact capacity.
• Check the pulse setting of the flowmeter.
CM2-MTG300-2001.book 7 ページ 2015年9月29日 火曜日 午前10時14分
Summary of Contents for MagneW Neo PLUS
Page 16: ...List of Figures Tables CM2 MTG300 2001 book 4...
Page 92: ...MEMO CM2 MTG300 2001 book 38...
Page 106: ...MEMO CM2 MTG300 2001 book 4...
Page 266: ...MEMO CM2 MTG300 2001 book 82...
Page 312: ...MEMO CM2 MTG300 2001 book 46...
Page 336: ...MEMO CM2 MTG300 2001 book 22...
Page 338: ...CM2 MTG300 2001 book 2...