Azbil Corporation
Operation using the data setting device
Model MTG11A/18A, MTG11B/18B, MTG14C
5-31
Selecting the Electrode Status Output Mode
Setting the output mode when the Electrode Status Diagnostic function detects the
empty or scale on electrode status.
There are the following three electrode status output modes.
• OFF
• ZERO
• HOLD
Default setting: OFF
Details of the “Electrode Status Output mode”
Output/Display
Parameter selection in the “Electrode status output mode”
OFF
ZERO
HOLD
Analog 4 – 20mA
output
Output values as the
meter measures.
Analog output is
fixed to 0% (4mA).
Analog output is
held at its last good
value.
Pulse output
Output values as the
meter measures.
Pulse output is fixed
to 0 (does not
generate pulses).
Pulse output is held
at its present state.
Display
Display the value as
it measures.
Flashes the message
0% and “Empty or
scale on electrode”
alternately (when %
flow rate is
specified for the
main display).
Flashes the message
0.000 RATE and
“Empty or scale on
electrode”
alternately (when
actual flow rate is
specified for the
main display).
Flashes the message
XXXXXXXX
(totalized value at
setup) and “Empty
or scale on
electrode”
alternately (when
totalized value is
specified for the
main display).
Flashes the values at
its last good values
and a message of
“Empty or scale on
electrode”
alternately.
CM2-MTG300-2001.book 31 ページ 2015年9月29日 火曜日 午前10時14分
Summary of Contents for MagneW Neo PLUS
Page 16: ...List of Figures Tables CM2 MTG300 2001 book 4...
Page 92: ...MEMO CM2 MTG300 2001 book 38...
Page 106: ...MEMO CM2 MTG300 2001 book 4...
Page 266: ...MEMO CM2 MTG300 2001 book 82...
Page 312: ...MEMO CM2 MTG300 2001 book 46...
Page 336: ...MEMO CM2 MTG300 2001 book 22...
Page 338: ...CM2 MTG300 2001 book 2...