Azbil Corporation
Operation using HART communicator
Model MTG11A/18A, MTG11B/18B, MTG14C
7-23
7-2-6 : Contact output setting
High alarm value setting
To set the high alarm value of contact output, proceeds as follows:
1.
From online menu,
Select:
1. Device setup
4. Detailed setup
2. Conf output
4. Digital output
1. Hi alarm
Figure 7-38 will then be displayed.
Figure 7-38
2.
Use the numeric keys to enter a high alarm value in the value input display.
Setting range of high alarm value is 0% to +115%. Do not set the value to be
High alarm value < Low alarm value.
3.
Once a new value is entered, press F4 (ENTER) to return to the Digital output
menu. When the value is outside the range, error will be displayed. Input the
value again.
4.
After returning to the Digital output menu, press F2 (SEND). Changed setting
will be transmitted to the converter. The HART communicator mark will
appear on the upper right hand corner while HART is communicating with the
device. The mark will disappear once communication has properly completed.