Azbil Corporation
Operation using the data setting device
Model MTG11A/18A, MTG11B/18B, MTG14C
6-11
6-1-3: SFC Wiring
Wiring between two wired magnetic flowmeter converter and SFC
This section describes the wiring method between the two wired magnetic flowmeter
converter and SFC.
Connect the SFC as shown in Figure 6-3.
Connect the SFC red terminal to I.OUT+ and the black terminal to I.OUT-.
6-1-4: SFC unavailable functions
There are functions which cannot be set or changed from SFC in two wired magnetic
flowmeter functions. These function settings or changing can be key operated from the
data setting device. To operate these functions, refer to “Chapter 5 : Operation using
the data setting device”.
Functions which cannot be set or changed using the SFC are,
• Auto spike cut
• Moving average processing
• Moving average processing time
• Pulse output adjustment
• Excitation current adjustment
Figure 6-3 SFC wiring connection
I.OUT +
I.OUT -
Red
Black
250
Ω
Host control
system
+
-
24V DC
SFC