Operation using the data setting device
Model MTG11A/18A, MTG11B/18B, MTG14C
5-25
(To the next page)
Step
Procedure
Screen
8
Repeat steps 1 to 5 to set SENSITIVITY MID,
SENSITIVITY LOW, SENSITIVITY LL or
SENSITIVITY LLL to check if the function also
detects the empty or scale on electrode status with
the converter's display.
Depending on whether the empty or scale on
electrode status is detected in each setting, the
result falls into one of the following.
(Results of electrode status diagnostic operation check in empty or scale on
electrode status)
• If the empty or scale on electrode status is not
detected when HIGH has been set (in the case of
result (6)), this function is not available in that
installation environment.
Repeat steps 1 to 5 to set the function to OFF.
Setting
Results (1)
Results (2)
Results (3)
Results (4)
Results (5)
Results (6)
LLL
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
LL
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
LOW
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
MID
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
HIGH
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
flashes
EMPTY OR
SCALE ON
ELECTRODE
does not flashes
CM2-MTG300-2001.book 25 ページ 2015年9月29日 火曜日 午前10時14分
Summary of Contents for MagneW Neo PLUS
Page 16: ...List of Figures Tables CM2 MTG300 2001 book 4...
Page 92: ...MEMO CM2 MTG300 2001 book 38...
Page 106: ...MEMO CM2 MTG300 2001 book 4...
Page 266: ...MEMO CM2 MTG300 2001 book 82...
Page 312: ...MEMO CM2 MTG300 2001 book 46...
Page 336: ...MEMO CM2 MTG300 2001 book 22...
Page 338: ...CM2 MTG300 2001 book 2...