Electrical wiring
Model MTG11A/18A, MTG11B/18B, MTG14C
3-3
See that the load resistance of the loop wiring should within the operational range
shown in Figure 3-1-1 with respect to the power supply voltage used.
~Note
A load resistance of at least 250W is needed for communication with the SFC or
HART communicator.
Figure 3-1-1 Supply power voltage-load resistance characteristics
Figure 3-1-2 Terminal block - Integral type
1164
385
250
0
15.3
21.05
24
42
21.05 < V < 30
R =
V–15.6
0.0218
30 < V < 42
R =
V–14.25
0.02383
Supply voltage(V DC)
1
2
Load resistance (
Ω
)
1
2
Power supply /
Signal terminal (4-20 mA)
Terminal for
communicator connection
Terminal for
pulse / contact output
Internal grounding terminal