Notes: Units DCF100TR-18HWWW DCF051DR-11DXY0 DCF053DR-11DPY0
SEPR
1,3,5
5.88
6.26
6.16
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1173022
548291
577476
Rated Refrigerant Capacity
P
A
1,3,5 kW
931.7
463.3
480.2
Rated Power Input D
A
kW
335.1
157.1
162.8
Rated EER
DC,A
2.78
2.95
2.95
Declared Refrigerant Capacity P
B
1,3,5 kW
926.4 / 815.9
517.3 / 424.3
536.3 / 442.4
Declared Power Input D
B
kW
242.9 / 209.2
129.9 / 103.2
134.5 / 107.7
Declared EER
DC,B
3.81 / 3.90
3.98 / 4.11
3.99 / 4.11
Declared Refrigerant Capacity P
C
1,3,5 kW
882.6 / 763.3
461.1 / 381.7
480.5 / 375.2
Declared Power Input D
C
kW
174.9 / 146.5
86.4 / 69.4
90.3 / 69.8
Declared EER
DC,C
5.05 / 5.21
5.34 / 5.50
5.32 / 5.37
Declared Refrigerant Capacity P
D
1,3,5 kW
739.9 / 670.0
367.8 / 287.5
380.7 / 253.2
Declared Power Input D
D
kW
90.2 / 103.9
42.0 / 43.3
44.4 / 39.2
Declared EER
DC,D
8.20 / 6.45
8.76 / 6.65
8.57 / 6.46
SSCEE
2,3,5
%
158.5
166.7
161.1
SSCEE Tier
6
Not Compliant
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
n/a
466.2
483.7
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
n/a
463.3
480.2
Declared EER
d
35°C
n/a
2.95
2.95
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
n/a
517.3 / 424.3
536.3 / 442.4
Declared EER
d
30°C
n/a
3.98 / 4.11
3.99 / 4.11
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
n/a
461.1 / 381.7
480.5 / 375.2
Declared EER
d
25°C
n/a
5.34 / 5.50
5.32 / 5.37
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
n/a
367.8 / 287.5
380.7 / 253.2
Declared EER
d
20°C
n/a
8.76 / 6.65
8.57 / 6.46
Sound Power Level LWA
dB(A)
n/a
90
91
Air flow rate
m³/h
n/a
232768
232768
Off mode P
OFF
kW
n/a
0.157
0.157
Thermostat-off mode P
TO
kW
n/a
3.216
3.940
Standby Mode P
SB
kW
n/a
0.286
0.274
Crankcase heater mode P
CK
kW
n/a
0.000
0.000
Technical Data
Ecodesign
DCF100TR-18HWWW, DCF051DR-11DXY0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections