DeltaChill™ Air Cooled and FreeCool
95
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
67
68
69
DCF057DX-13DYV0
DCF057DX-14DYY0
DCF060DX-14DVV0
FreeCooling
Yes
Yes
Yes
Enhance Capital Allowance
No
No
No
Number of Refrigeration Circuits
2
2
2
Cooling Duty - EC Fans
Nominal Output - Mechanical
(1) kW
563.9
555.9
586.7
Nominal Input - Mechanical
kW
181.7
172.6
185.4
EER
(2)
3.10
3.22
3.16
ESEER
4.19
4.27
4.24
Nominal Output - Free Cooling
kW
463.7
484.1
493.6
Ambient temperature for
100% Free Cooling
(5) °C
0.4
1.2
0.7
Capacity Steps
%
15-35-50-70-85-100
20-35-50-70-85-100
20-35-55-70-85-100
Minimum Turndown Ratio
0.17
0.18
0.18
Dimensions (H x W x L)
mm
2682 x 2200 x 8242
2682 x 2200 x 8242
2682 x 2200 x 8242
Weight
Machine
(3) kg
6400
6465
6510
Operating
kg
7340
7435
7480
Water Volume (Total Internal)
l
940
970
970
Maximum Waterflow
l/s
46.7
46.7
46.7
Minimum Waterflow
l/s
10.7
10.7
10.7
Face Area (Total)
m²
2.38
2.38
2.38
Nominal Airflow - EC Fans
m³/s
52.0
56.0
56.0
Quantity
13
14
14
Maximum Speed - EC Fans
rpm
725
725
725
Compressor
Trio + Trio
Trio + Trio
Trio + Trio
Quantity of Compressors
6
6
6
Oil Charge Volume (Total)
l
3 x 5.3 + 3 x 5.3
3 x 5.3 + 3 x 5.3
3 x 5.3 + 3 x 5.3
Refrigeration
R410A / 2088
Charge (Total)
kg
35 + 39
39 + 38
40 + 39
GWP Tonnes Equivalent CO
2
tCO2
73 + 81
81 + 79
84 + 81
Refrigerant Control
Electronic Expansion Valve (EEV)
Water Inlet / Outlet - Unit
DN125
DN125
DN125
Water Drain / Bleed - Evap
inch
1/2
1/2
1/2
Water System
Minimum System Water Volume
(4)
l
1789
1800
1912
Maximum System
Operating Pressure
Bar
10
10
10
(1)
Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
All performance data supplied in accordance with BBS EN14511-1:2013
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power),
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations
(5)
Ambient temperature that full Freecool capacity can be achieved
DCF Mechanical Data Extra Quiet