DeltaChill™ Air Cooled and FreeCool
169
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
134
135
136
DCC088TR-18GVVW DCC091TR-18GVWW DCC094TR-18GWWW
FreeCooling
No
No
No
Enhance Capital Allowance
No
No
No
Number of Refrigeration Circuits
3
3
3
Cooling Duty - EC Fans
Nominal Output - Mechanical
(1) kW
869.2
900.5
931.7
Nominal Input - Mechanical
kW
292.3
306.9
321.5
EER
(2)
2.97
2.93
2.90
ESEER
4.33
4.28
4.21
Nominal Output - Free Cooling
kW
N/A
N/A
N/A
Ambient temperature for
100% Free Cooling
(5) °C
N/A
N/A
N/A
Capacity Steps
%
10-20-35-45-55-
70-80-90-100
10-25-35-45-55-
70-80-90-100
10-25-35-45-55-
70-80-90-100
Minimum Turndown Ratio
0.11
0.11
0.12
Dimensions (H x W x L)
mm
2682 x 2200 x 10506
2682 x 2200 x 10506
2682 x 2200 x 10506
Weight
Machine
(3) kg
7230
7255
7285
Operating
kg
7900
7925
7955
Water Volume (Total Internal)
l
670
670
670
Maximum Waterflow
l/s
63.1
63.1
63.1
Minimum Waterflow
l/s
14.1
14.1
14.1
Face Area (Total)
m²
2.38
2.38
2.38
Nominal Airflow - EC Fans
m³/s
116.0
116.0
116.0
Quantity
18
18
18
Maximum Speed - EC Fans
rpm
1026
1026
1026
Compressor
Trio + Trio + Trio
Trio + Trio + Trio
Trio + Trio + Trio
Quantity of Compressors
9
9
9
Oil Charge Volume (Total)
l
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
Refrigeration
R410A / 2088
Charge (Total)
kg
36 + 38 + 39
36 + 38 + 39
36 + 38 + 39
GWP Tonnes Equivalent CO2
tCO2
75 + 79 + 81
75 + 79 + 81
75 + 79 + 81
Refrigerant Control
Electronic Expansion Valve (EEV)
Water Inlet / Outlet - Unit
DN150
DN150
DN150
Water Drain / Bleed - Evap
inch
1/2
1/2
1/2
Water System
Minimum System Water Volume
(4)
l
1675
1675
1868
Maximum System
Operating Pressure
Bar
10
10
10
DCC Mechanical Data - Regular Quiet
(1)
Based on units performance at 12/7°C return/supply temperatures, 35°C ambient, 100% water. All performance data supplied in accordance with BBS EN14511-1:2013
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power),
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations
(5)
Ambient temperature that full Freecool capacity can be achieved