Technical Data
Ecodesign
DCC015DX-04ADF0, DCC016DX-04AJJ0, DCC018DX-04BJK0
Notes: Units DCC090TR-21GVVW DCC093TR-21GVWW DCC096TR-21GWWW
SEPR
1,3,5
5.77
5.71
5.64
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1125163
1177854
1233281
Rated Refrigerant Capacity
P
A
1,3,5 kW
876.9
908
939.1
Rated Power Input D
A
kW
286.6
300.7
315.1
Rated EER
DC,A
3.06
3.02
2.98
Declared Refrigerant Capacity P
B
1,3,5 kW
862.3 / 761.1
896.4 / 784.5
930.5 / 818.6
Declared Power Input D
B
kW
203.8 / 177.0
215.7 / 184.4
227.6 / 196.3
Declared EER
DC,B
4.23 / 4.30
4.16 / 4.26
4.09 / 4.17
Declared Refrigerant Capacity P
C
1,3,5 kW
822.1 / 713.3
846.8 / 738.0
882.7 / 762.6
Declared Power Input D
C
kW
147.3 / 124.8
153.5 / 131.0
163.5 / 137.1
Declared EER
DC,C
5.58 / 5.72
5.52 / 5.64
5.40 / 5.56
Declared Refrigerant Capacity P
D
1,3,5 kW
739.0 / 606.4
765.9 / 633.2
792.7 / 660.0
Declared Power Input D
D
kW
109.5 / 90.0
114.2 / 94.8
118.9 / 99.5
Declared EER
DC,D
6.75 / 6.73
6.71 / 6.68
6.66 / 6.63
SSCEE
2,3,5
%
178.9
176.5
173.6
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
879.5
910.8
942.1
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
876.9
908
939.1
Declared EER
d
35°C
3.06
3.02
2.98
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
862.3 / 761.1
896.4 / 784.5
930.5 / 818.6
Declared EER
d
30°C
4.23 / 4.30
4.16 / 4.26
4.09 / 4.17
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
822.1 / 713.3
846.8 / 738.0
882.7 / 762.6
Declared EER
d
25°C
5.58 / 5.72
5.52 / 5.64
5.40 / 5.56
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
739.0 / 606.4
765.9 / 633.2
792.7 / 660.0
Declared EER
d
20°C
6.75 / 6.73
6.71 / 6.68
6.66 / 6.63
Sound Power Level LWA
dB(A)
94
94
95
Air flow rate
m³/h
487187
487187
487187
Off mode P
OFF
kW
0.169
0.169
0.169
Thermostat-off mode P
TO
kW
3.313
3.607
3.916
Standby Mode P
SB
kW
0.383
0.383
0.383
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
252
Chiller Technical Manual 7267818 V1.13.0_01_2018