DeltaChill™ Air Cooled and FreeCool
191
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
113
114
115
Unit Data
DCC069TR-11GPYY
DCC074TR-12GYYY
DCC056DR-13DYV0
Nominal Run Amps
(1)
A
470.1
500.1
376.9
Maximum Start Amps
A
733.5
775.7
644.3
Recommended Mains Fuse Size
A
500
560
400
Evaporator
Immersion Heater Rating
W
250
250
170
Condenser Fan - Per Fan (EC)
Quantity
11
12
13
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 47.9 / 47.9
47.9 / 47.9 / 47.9
47.9 / 55.2
Quantity
2 + 3 + 3
3 + 3 + 3
3 + 3
Motor Rating
kW
36.2 / 29.8 / 29.8
29.8 / 29.8 / 29.8
29.8 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 326 / 326
326 / 326 / 326
326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
446.3
477.4
355.0
Reactive power reduction/saving
(4)
kVAr
44.1
42.7
39.8
Maximum Start Amps
A
709.7
753.0
622.4
Recommended Mains Fuse Size
A
500
560
400
Electronic Soft-start
Nominal Run Amps
A
470.1
500.1
376.9
Maximum Start Amps
A
603.1
645.3
513.9
Recommended Mains Fuse
A
500
560
400
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
446.3
477.4
355.0
Maximum Start Amps
A
579.3
622.6
492.0
Recommended Mains Fuse Size
A
500
560
400
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
8.9
Unit Nominal Run Amps
A
481.1
511.0
385.4
Recommended Mains Fuse Size
A
500
560
450
Motor Rating
kW
6.2
6.2
4.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
11.2
Unit Nominal Run Amps
A
491.0
521.0
387.9
Recommended Mains Fuse Size
A
560
560
450
Motor Rating
kW
12.1
12.1
6.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.2
10.2
7.3
Unit Nominal Run Amps
A
478.4
508.4
382.8
Recommended Mains Fuse Size
A
500
560
400
Motor Rating
kW
6.4
6.4
4.5
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
10.1
Unit Nominal Run Amps
A
486.3
516.3
385.1
Recommended Mains Fuse Size
A
560
560
450
Motor Rating
kW
12.4
12.4
6.3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Regular Quiet