Notes: Units DCF068DX-14FWW0 DCF073TX-16GPPY DCF078TX-17GPYY
SEPR
1,3,5
6.47
6.54
6.48
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
704999
756106
820674
Rated Refrigerant Capacity
P
A
1,3,5 kW
615.2
667.5
717.3
Rated Power Input D
A
kW
217.4
231.8
250.8
Rated EER
DC,A
2.83
2.88
2.86
Declared Refrigerant Capacity P
B
1,3,5 kW
590.3 / 482.6
667.3 / 572.2
723.1 / 634.0
Declared Power Input D
B
kW
146.9 / 114.8
164.8 / 140.5
180.7 / 154.2
Declared EER
DC,B
4.02 / 4.20
4.05 / 4.07
4.00 / 4.11
Declared Refrigerant Capacity P
C
1,3,5 kW
645.4 / 523.4
627.7 / 501.7
691.8 / 587.1
Declared Power Input D
C
kW
123.0 / 95.8
118.0 / 91.7
129.3 / 108.9
Declared EER
DC,C
5.25 / 5.46
5.32 / 5.47
5.35 / 5.39
Declared Refrigerant Capacity P
D
1,3,5 kW
488.4 / 411.2
530.2 / 525.8
569.2 / 504.8
Declared Power Input D
D
kW
50.5 / 62.5
52.5 / 80.4
58.0 / 78.2
Declared EER
DC,D
9.68 / 6.58
10.10 / 6.54
9.82 / 6.46
SSCEE
2,3,5
%
164.9
162.5
162.4
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
619.1
671.3
722
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
615.2
667.5
717.3
Declared EER
d
35°C
2.83
2.88
2.86
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
590.3 / 482.6
667.3 / 572.2
723.1 / 634.0
Declared EER
d
30°C
4.02 / 4.20
4.05 / 4.07
4.00 / 4.11
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
645.4 / 523.4
627.7 / 501.7
691.8 / 587.1
Declared EER
d
25°C
5.25 / 5.46
5.32 / 5.47
5.35 / 5.39
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
488.4 / 411.2
530.2 / 525.8
569.2 / 504.8
Declared EER
d
20°C
9.68 / 6.58
10.10 / 6.54
9.82 / 6.46
Sound Power Level LWA
dB(A)
Air flow rate
m³/h
201476
230259
244650
Off mode P
OFF
kW
0.157
0.169
0.169
Thermostat-off mode P
TO
kW
4.295
4.374
5.300
Standby Mode P
SB
kW
0.301
0.335
0.351
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Technical Data
Ecodesign
DCF047DX-09DXY0, DCF049DX-09DPY0, DCF051DX-10DPV0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections