Notes: Units DCF098TR-21HVVW DCF101TR-21HVWW DCF103TR-21HWWW
SEPR
1,3,5
6.23
6.17
6.10
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1054355
1101407
1146261
Rated Refrigerant Capacity
P
A
1,3,5 kW
886.6
917.8
943.6
Rated Power Input D
A
kW
297.5
312.2
325.4
Rated EER
DC,A
2.98
2.94
2.9
Declared Refrigerant Capacity P
B
1,3,5 kW
874.4 / 771.8
908.7 / 795.3
937.9 / 825.3
Declared Power Input D
B
kW
212.1 / 184.4
224.7 / 192.3
235.6 / 203.3
Declared EER
DC,B
4.12 / 4.19
4.04 / 4.14
3.98 / 4.06
Declared Refrigerant Capacity P
C
1,3,5 kW
835.7 / 725.0
860.7 / 750.0
892.4 / 771.0
Declared Power Input D
C
kW
154.0 / 130.8
160.6 / 137.4
169.7 / 142.5
Declared EER
DC,C
5.43 / 5.54
5.36 / 5.46
5.26 / 5.41
Declared Refrigerant Capacity P
D
1,3,5 kW
703.9 / 619.0
728.4 / 646.3
749.7 / 670.2
Declared Power Input D
D
kW
82.6 / 93.8
85.4 / 98.9
88.8 / 102.6
Declared EER
DC,D
8.53 / 6.60
8.53 / 6.54
8.45 / 6.53
SSCEE
2,3,5
%
166.1
163.4
163.8
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
892.1
923.7
948.9
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
886.6
917.8
943.6
Declared EER
d
35°C
2.98
2.94
2.9
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
874.4 / 771.8
908.7 / 795.3
937.9 / 825.3
Declared EER
d
30°C
4.12 / 4.19
4.04 / 4.14
3.98 / 4.06
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
835.7 / 725.0
860.7 / 750.0
892.4 / 771.0
Declared EER
d
25°C
5.43 / 5.54
5.36 / 5.46
5.26 / 5.41
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
703.9 / 619.0
728.4 / 646.3
749.7 / 670.2
Declared EER
d
20°C
8.53 / 6.60
8.53 / 6.54
8.45 / 6.53
Sound Power Level LWA
dB(A)
94
95
95
Air flow rate
m³/h
444376
444376
444376
Off mode P
OFF
kW
0.169
0.169
0.169
Thermostat-off mode P
TO
kW
6.380
6.946
6.239
Standby Mode P
SB
kW
0.383
0.383
0.383
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Technical Data
Ecodesign
DCF098TR-21HVVW, DCF101TR-21HVWW, DCF103TR-21HWWW
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
283
Chiller Technical Manual 7267818 V1.13.0_01_2018