Technical Data
Ecodesign
DCC049DR-10EPV0, DCC051DR-10EYY0, DCC054DR-11DYV0
Notes: Units DCC049DR-10EPV0 DCC051DR-10EYY0 DCC054DR-11DYV0
SEPR
1,3,5
5.36
5.32
5.56
SEPR Tier
Tier 1 (2018)
Tier 1 (2018)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
664864
701245
713403
Rated Refrigerant Capacity
P
A
1,3,5 kW
480.7
503.4
535
Rated Power Input D
A
kW
165.8
179.1
183.2
Rated EER
DC,A
2.9
2.81
2.92
Declared Refrigerant Capacity P
B
1,3,5 kW
532.7 / 436.2
556.1 / 467.1
593.0 / 494.1
Declared Power Input D
B
kW
135.9 / 108.3
147.8 / 120.8
150.5 / 122.7
Declared EER
DC,B
3.92 / 4.03
3.76 / 3.87
3.94 / 4.03
Declared Refrigerant Capacity P
C
1,3,5 kW
469.8 / 363.2
502.1 / 406.4
532.0 / 434.0
Declared Power Input D
C
kW
90.4 / 69.4
101.0 / 78.1
102.5 / 79.5
Declared EER
DC,C
5.19 / 5.23
4.97 / 5.20
5.19 / 5.46
Declared Refrigerant Capacity P
D
1,3,5 kW
492.7 / 380.1
424.7 / 318.0
453.3 / 336.2
Declared Power Input D
D
kW
77.9 / 60.8
66.7 / 50.4
68.3 / 51.1
Declared EER
DC,D
6.32 / 6.25
6.36 / 6.31
6.63 / 6.58
SSCEE
2,3,5
%
164.3
163.3
172.0
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
482.6
505.5
536.5
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
480.7
503.4
535
Declared EER
d
35°C
2.9
2.81
2.92
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
532.7 / 436.2
556.1 / 467.1
593.0 / 494.1
Declared EER
d
30°C
3.92 / 4.03
3.76 / 3.87
3.94 / 4.03
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
469.8 / 363.2
502.1 / 406.4
532.0 / 434.0
Declared EER
d
25°C
5.19 / 5.23
4.97 / 5.20
5.19 / 5.46
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
492.7 / 380.1
424.7 / 318.0
453.3 / 336.2
Declared EER
d
20°C
6.32 / 6.25
6.36 / 6.31
6.63 / 6.58
Sound Power Level LWA
dB(A)
92
92
92
Air flow rate
m³/h
231994
231994
255193
Off mode P
OFF
kW
0.157
0.157
0.157
Thermostat-off mode P
TO
kW
2.256
2.522
1.932
Standby Mode P
SB
kW
0.269
0.281
0.286
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
243
Chiller Technical Manual 7267818 V1.13.0_01_2018