Notes: Units DCF099TX-21HWWW DCF050DX-13DXY0 DCF053DX-13DPY0
SEPR
1,3,5
6.46
6.81
6.72
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1046771
504988
529282
Rated Refrigerant Capacity
P
A
1,3,5 kW
913
464.1
480.1
Rated Power Input D
A
kW
323.8
151.7
156.9
Rated EER
DC,A
2.82
3.06
3.06
Declared Refrigerant Capacity P
B
1,3,5 kW
926.4 / 819.7
522.5 / 429.3
541.0 / 446.8
Declared Power Input D
B
kW
234.6 / 202.6
125.8 / 100.3
130.0 / 104.3
Declared EER
DC,B
3.95 / 4.05
4.15 / 4.28
4.16 / 4.28
Declared Refrigerant Capacity P
C
1,3,5 kW
891.6 / 771.4
466.6 / 385.7
486.4 / 379.7
Declared Power Input D
C
kW
169.1 / 142.1
83.7 / 67.5
87.5 / 67.7
Declared EER
DC,C
5.27 / 5.43
5.57 / 5.71
5.56 / 5.61
Declared Refrigerant Capacity P
D
1,3,5 kW
725.6 / 670.6
368.6 / 287.7
380.8 / 253.5
Declared Power Input D
D
kW
74.1 / 102.2
35.9 / 42.9
37.8 / 38.9
Declared EER
DC,D
9.79 / 6.56
10.26 / 6.70
10.06 / 6.52
SSCEE
2,3,5
%
164.7
172.3
167.0
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
917.9
466.7
483.4
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
913
464.1
480.1
Declared EER
d
35°C
2.82
3.06
3.06
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
926.4 / 819.7
522.5 / 429.3
541.0 / 446.8
Declared EER
d
30°C
3.95 / 4.05
4.15 / 4.28
4.16 / 4.28
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
891.6 / 771.4
466.6 / 385.7
486.4 / 379.7
Declared EER
d
25°C
5.27 / 5.43
5.57 / 5.71
5.56 / 5.61
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
725.6 / 670.6
368.6 / 287.7
380.8 / 253.5
Declared EER
d
20°C
9.79 / 6.56
10.26 / 6.70
10.06 / 6.52
Sound Power Level LWA
dB(A)
Air flow rate
m³/h
302214
187085
187085
Off mode P
OFF
kW
0.169
0.157
0.157
Thermostat-off mode P
TO
kW
5.755
3.045
3.741
Standby Mode P
SB
kW
0.383
0.296
0.284
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Technical Data
Ecodesign
DCF099TX-21HWWW, DCF050DX-13DXY0, DCF053DX-13DPY0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
295
Chiller Technical Manual 7267818 V1.13.0_01_2018