Technical Data
Ecodesign
DCC059DR-14DVV0, DCC061DR-14DVW0, DCC065DR-14DWW0
Notes: Units DCC059DR-14DVV0 DCC061DR-14DVW0 DCC065DR-14DWW0
SEPR
1,3,5
5.78
5.70
5.60
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
727164
773760
837292
Rated Refrigerant Capacity
P
A
1,3,5 kW
567.6
595.5
633.1
Rated Power Input D
A
kW
182.5
196.5
211.7
Rated EER
DC,A
3.11
3.03
2.99
Declared Refrigerant Capacity P
B
1,3,5 kW
630.0 / 528.1
660.3 / 548.5
702.8 / 589.5
Declared Power Input D
B
kW
149.9 / 123.0
161.0 / 129.7
174.5 / 143.1
Declared EER
DC,B
4.20 / 4.29
4.10 / 4.23
4.03 / 4.12
Declared Refrigerant Capacity P
C
1,3,5 kW
569.7 / 460.2
590.9 / 482.1
635.7 / 514.0
Declared Power Input D
C
kW
102.6 / 80.1
108.1 / 85.6
119.7 / 93.2
Declared EER
DC,C
5.55 / 5.75
5.47 / 5.63
5.31 / 5.52
Declared Refrigerant Capacity P
D
1,3,5 kW
475.7 / 356.1
499.1 / 367.3
534.8 / 400.3
Declared Power Input D
D
kW
70.8 / 53.6
74.9 / 55.4
81.0 / 61.4
Declared EER
DC,D
6.72 / 6.65
6.67 / 6.63
6.61 / 6.52
SSCEE
2,3,5
%
176.2
175.8
168.1
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
570
597.7
636.5
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
567.6
595.5
633.1
Declared EER
d
35°C
3.11
3.03
2.99
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
630.0 / 528.1
660.3 / 548.5
702.8 / 589.5
Declared EER
d
30°C
4.20 / 4.29
4.10 / 4.23
4.03 / 4.12
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
569.7 / 460.2
590.9 / 482.1
635.7 / 514.0
Declared EER
d
25°C
5.55 / 5.75
5.47 / 5.63
5.31 / 5.52
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
475.7 / 356.1
499.1 / 367.3
534.8 / 400.3
Declared EER
d
20°C
6.72 / 6.65
6.67 / 6.63
6.61 / 6.52
Sound Power Level LWA
dB(A)
91
92
93
Air flow rate
m³/h
324791
324791
324791
Off mode P
OFF
kW
0.157
0.157
0.157
Thermostat-off mode P
TO
kW
2.909
2.677
4.074
Standby Mode P
SB
kW
0.301
0.301
0.301
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
249
Chiller Technical Manual 7267818 V1.13.0_01_2018