Technical Data
Ecodesign
DCC080TR-16GYYV, DCC082TR-17GYVV, DCC085TR-18GVVV
Notes: Units DCC080TR-16GYYV DCC082TR-17GYVV DCC085TR-18GVVV
SEPR
1,3,5
5.50
5.54
5.59
SEPR Tier
Tier 1 (2018)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1062924
1080748
1095752
Rated Refrigerant Capacity
P
A
1,3,5 kW
788.4
807.8
827.1
Rated Power Input D
A
kW
272.8
276.6
280.4
Rated EER
DC,A
2.89
2.92
2.95
Declared Refrigerant Capacity P
B
1,3,5 kW
776.1 / 685.2
797.8 / 699.3
819.5 / 721.0
Declared Power Input D
B
kW
197.2 / 170.0
199.6 / 171.8
202.0 / 174.2
Declared EER
DC,B
3.94 / 4.03
4.00 / 4.07
4.06 / 4.14
Declared Refrigerant Capacity P
C
1,3,5 kW
738.9 / 641.3
754.0 / 656.4
777.2 / 671.4
Declared Power Input D
C
kW
142.0 / 119.0
143.4 / 120.4
145.1 / 121.8
Declared EER
DC,C
5.20 / 5.39
5.26 / 5.45
5.36 / 5.51
Declared Refrigerant Capacity P
D
1,3,5 kW
671.6 / 554.6
685.0 / 568.1
698.5 / 581.5
Declared Power Input D
D
kW
102.1 / 84.8
103.9 / 86.7
105.7 / 88.5
Declared EER
DC,D
6.58 / 6.54
6.59 / 6.56
6.61 / 6.57
SSCEE
2,3,5
%
168.3
169.2
171.0
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
791.2
810.7
830.3
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
788.4
807.8
827.1
Declared EER
d
35°C
2.89
2.92
2.95
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
776.1 / 685.2
797.8 / 699.3
819.5 / 721.0
Declared EER
d
30°C
3.94 / 4.03
4.00 / 4.07
4.06 / 4.14
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
738.9 / 641.3
754.0 / 656.4
777.2 / 671.4
Declared EER
d
25°C
5.20 / 5.39
5.26 / 5.45
5.36 / 5.51
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
671.6 / 554.6
685.0 / 568.1
698.5 / 581.5
Declared EER
d
20°C
6.58 / 6.54
6.59 / 6.56
6.61 / 6.57
Sound Power Level LWA
dB(A)
94
94
94
Air flow rate
m³/h
371190
394390
417589
Off mode P
OFF
kW
0.169
0.169
0.169
Thermostat-off mode P
TO
kW
3.393
3.620
3.835
Standby Mode P
SB
kW
0.358
0.363
0.368
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
246
Chiller Technical Manual 7267818 V1.13.0_01_2018