Chillers
DeltaChill™Air Cooled and FreeCool
29
Chiller Technical Manual 7267818 V1.13.0_01_2018
Installation Data
Weights, Point Loadings & Centre of Gravity (C of G) DCF
(1) Point load numbering starts from the control panel end of the chiller. Illustration above is for a 8 mount configuration
(2) Point loads indicated are for standard unit only
2
1
L1
L2
L3
L4
R1
R2
R3
R4
= C of G
Point load
L1
L2
L3
L4
L5
L6
L7
R1
R2
R3
R4
R5
R6
R7
C of
G 1
C of
G 2
kg
mm mm
1 DCF046DR-07DXY0
650 745 820
810 925 1020
985 2480
2 DCF048DR-07DPY0
620 740 840
750 890 1010
1000 2545
3 DCF051DR-08DPV0
655 755 840
785 910 1010
1005 2500
4 DCF053DR-08DYY0
685 760 825
850 945 1025
985 2440
5 DCF049DR-09DXY0
675 660 645 630
800 780 765 745
1015 2755
6 DCF051DR-09DPY0
695 675 665 650
820 800 785 765
1015 2755
7 DCF053DR-10DPV0
710 695 680 665
840 820 805 785
1010 2760
8 DCF055DR-09DYV0
715 695 680 665
855 830 815 795
1005 2750
9 DCF055DR-10DYY0
720 740 760 785
840 870 895 920
1015 2950
10 DCF058DR-10DVV0
850 845 845 845
1015 1010 1010 1005
1005 3395
11 DCF062DR-10FVW0
895 875 855 830
1090 1065 1040 1010
995 3290
12 DCF065DR-10FWW0 840 815 790 815 745
945 915 885 915 835
1040 3750
13 DCF069TR-10GPPY
850 825 800 825 755
955 925 900 925 850
1040 3765
14 DCF051DR-11DXY0
945 895 845 895 770
1040 990 930 990 850
1050 4215
15 DCF053DR-11DPY0
950 900 850 900 775
1055 1000 940 1000 860
1045 4220
16 DCF055DR-12DPV0
950 905 850 905 775
1065 1010 950 1010 865
1040 4215
17 DCF057DR-12DYY0
955 905 850 905 775
1075 1020 960 1020 870
1035 4200
18 DCF058DR-11DYV0
675 660 650 635
795 775 760 745
1015 2760
19 DCF060DR-12DVV0
655 650 650 645
750 745 740 740
1030 2820
20 DCF065DR-12FVW0
670 665 665 660
765 760 755 750
1030 2820
21 DCF068DR-12FWW0 690 675 660 645
810 795 780 760
1015 2760
22 DCF074TR-11GPYY
795 765 735 695
900 865 830 790
1035 3210
23 DCF079TR-12GYYY
820 785 745 700
930 885 840 790
1035 3165
24 DCF059DR-13DYV0
850 810 765 710
950 905 855 800
1040 3140
25 DCF062DR-14DVV0
855 820 780 735
995 955 910 855
1020 3180