Chillers
DeltaChill™ Air Cooled and FreeCool
137
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
ELECTRICAL DATA
94
95
96
97
Unit Data
DCF092TX-
21HVVV
DCF095TX-
21HVVW
DCF097TX-
21HVWW
DCF099TX-
21HWWW
Nominal Run Amps
(1)
A
608.0
620.1
632.2
644.4
Maximum Start Amps
A
875.4
883.5
895.6
879.8
Recommended Mains Fuse Size
A
630
670
670
670
Evaporator
Immersion Heater Rating
W
250
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
21
21
21
21
Full Load Amps
A
3.9
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
2.56
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2 / 55.2 55.2 / 55.2 / 59.2 55.2 / 59.2 / 59.2 59.2 / 59.2 / 59.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
33.1 / 33.1 / 33.1 33.1 / 33.1 / 36.2 33.1 / 36.2 / 36.2 36.2 / 36.2 / 36.2
Sump Heater Rating
W
140
140
140
140
Start Amps
(2)
A
326 / 326 / 326
326 / 326 / 298
326 / 298 / 298
298 / 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
564.4
578.0
591.7
605.4
Reactive power reduction/saving
(4) kVAr
76.6
74.5
72.4
70.3
Maximum Start Amps
A
831.8
841.4
855.1
840.8
Recommended Mains Fuse Size
A
630
670
670
670
Electronic Soft-start
Nominal Run Amps
A
608.0
620.1
632.2
644.4
Maximum Start Amps
A
745.0
753.1
765.2
760.6
Recommended Mains Fuse
A
630
670
670
670
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
564.4
578.0
591.7
605.4
Maximum Start Amps
A
701.4
711.0
724.7
721.6
Recommended Mains Fuse Size
A
630
670
670
670
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
35.0
Unit Nominal Run Amps
A
636.4
648.4
660.5
679.1
Recommended Mains Fuse Size
A
670
670
710
710
Motor Rating
kW
16.4
16.4
16.4
20.3
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
35.0
41.5
Unit Nominal Run Amps
A
642.9
654.9
667.0
685.6
Recommended Mains Fuse Size
A
670
710
710
710
Motor Rating
kW
20.3
20.3
20.3
23.9
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
33.2
Unit Nominal Run Amps
A
629.5
641.6
653.8
671.2
Recommended Mains Fuse Size
A
670
670
710
710
Motor Rating
kW
16.8
16.8
16.8
20.7
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
33.2
39.2
Unit Nominal Run Amps
A
634.5
646.7
658.9
676.0
Recommended Mains Fuse Size
A
670
710
710
710
Motor Rating
kW
20.7
20.7
20.7
24.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet