ELECTRICAL DATA
64
65
66
Unit Data
DCF050DX-13DXY0
DCF053DX-13DPY0
DCF055DX-14DPV0
Nominal Run Amps
(1)
A
316.2
326.6
354.8
Maximum Start Amps
A
591.8
590.0
618.2
Recommended Mains Fuse Size
A
355
355
400
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
13
13
14
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
36 / 47.9
59.2 / 47.9
59.2 / 55.2
Quantity
3 + 3
2 + 3
2 + 3
Motor Rating
kW
22.7 / 29.8
36.2 / 29.8
36.2 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
210 / 326
298 / 326
298 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
304.4
310.5
331.7
Reactive power reduction/saving
(4) kVAr
22.7
30.0
41.2
Maximum Start Amps
A
580.0
573.9
595.1
Recommended Mains Fuse Size
A
355
355
400
Electronic Soft-start
Nominal Run Amps
A
316.2
326.6
354.8
Maximum Start Amps
A
461.4
459.6
487.8
Recommended Mains Fuse
A
355
355
400
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
304.4
310.5
331.7
Maximum Start Amps
A
449.6
443.5
464.7
Recommended Mains Fuse Size
A
355
355
400
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
14.8
Unit Nominal Run Amps
A
330.7
341.2
369.5
Recommended Mains Fuse Size
A
355
400
400
Motor Rating
kW
8.4
8.4
8.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
337.1
347.6
375.9
Recommended Mains Fuse Size
A
355
400
400
Motor Rating
kW
12.1
12.1
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
13.9
13.9
13.9
Unit Nominal Run Amps
A
327.7
337.9
365.9
Recommended Mains Fuse Size
A
355
400
400
Motor Rating
kW
8.6
8.6
8.6
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
332.6
342.8
370.8
Recommended Mains Fuse Size
A
355
400
400
Motor Rating
kW
12.4
12.4
12.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet