Chillers
DeltaChill™ Air Cooled and FreeCool
128
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
ni
ca
l
Fr
ee
C
oo
l
ELECTRICAL DATA
67
68
69
Unit Data
DCF057DX-13DYV0
DCF057DX-14DYY0
DCF060DX-14DVV0
Nominal Run Amps
(1)
A
376.9
356.7
405.3
Maximum Start Amps
A
644.3
632.3
672.7
Recommended Mains Fuse Size
A
400
400
450
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
13
14
14
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.9 / 55.2
47.9 / 47.9
55.2 / 55.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
29.8 / 33.1
29.8 / 29.8
33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326
326 / 326
326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
355.0
341.6
376.3
Reactive power reduction/saving
(4) kVAr
39.8
28.6
51.0
Maximum Start Amps
A
622.4
617.2
643.7
Recommended Mains Fuse Size
A
400
400
450
Electronic Soft-start
Nominal Run Amps
A
376.9
356.7
405.3
Maximum Start Amps
A
513.9
501.9
542.3
Recommended Mains Fuse
A
400
400
450
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
355.0
341.6
376.3
Maximum Start Amps
A
492.0
486.8
513.3
Recommended Mains Fuse Size
A
400
400
450
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
21.2
Unit Nominal Run Amps
A
391.6
371.2
426.4
Recommended Mains Fuse Size
A
450
400
450
Motor Rating
kW
8.4
8.4
12.1
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
28.5
Unit Nominal Run Amps
A
398.0
377.6
433.7
Recommended Mains Fuse Size
A
450
400
450
Motor Rating
kW
12.1
12.1
16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
13.9
13.9
19.8
Unit Nominal Run Amps
A
388.1
368.0
421.2
Recommended Mains Fuse Size
A
450
400
450
Motor Rating
kW
8.6
8.6
12.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
26.9
Unit Nominal Run Amps
A
393.0
373.0
426.9
Recommended Mains Fuse Size
A
450
400
450
Motor Rating
kW
12.4
12.4
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet