Technical Data
Ecodesign
DCC077TR-13GYYV, DCC080TR-14GYVV, DCC083TR-15GVVV
Notes: Units DCC077TR-13GYYV DCC080TR-14GYVV DCC083TR-15GVVV
SEPR
1,3,5
5.27
5.34
5.43
SEPR Tier
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Annual Electricity Consumption
kWh/a
1079383
1097288
1111590
Rated Refrigerant Capacity
P
A
1,3,5 kW
767
790.7
814.3
Rated Power Input D
A
kW
282.0
286.5
289.8
Rated EER
DC,A
2.72
2.76
2.81
Declared Refrigerant Capacity P
B
1,3,5 kW
763.7 / 675.0
786.2 / 689.6
808.6 / 712.0
Declared Power Input D
B
kW
205.6 / 176.6
207.3 / 178.1
209.0 / 179.9
Declared EER
DC,B
3.71 / 3.82
3.79 / 3.87
3.87 / 3.96
Declared Refrigerant Capacity P
C
1,3,5 kW
727.4 / 632.7
743.1 / 648.4
767.7 / 664.0
Declared Power Input D
C
kW
147.9 / 123.3
149.0 / 124.4
150.1 / 125.5
Declared EER
DC,C
4.92 / 5.13
4.99 / 5.21
5.11 / 5.29
Declared Refrigerant Capacity P
D
1,3,5 kW
669.4 / 552.4
684.0 / 567.1
698.7 / 581.7
Declared Power Input D
D
kW
104.9 / 87.2
105.9 / 88.2
106.9 / 89.2
Declared EER
DC,D
6.38 / 6.33
6.46 / 6.43
6.53 / 6.52
SSCEE
2,3,5
%
162.4
163.6
165.9
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
769.6
793.5
817.3
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
767
790.7
814.3
Declared EER
d
35°C
2.72
2.76
2.81
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
763.7 / 675.0
786.2 / 689.6
808.6 / 712.0
Declared EER
d
30°C
3.71 / 3.82
3.79 / 3.87
3.87 / 3.96
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
727.4 / 632.7
743.1 / 648.4
767.7 / 664.0
Declared EER
d
25°C
4.92 / 5.13
4.99 / 5.21
5.11 / 5.29
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
669.4 / 552.4
684.0 / 567.1
698.7 / 581.7
Declared EER
d
20°C
6.38 / 6.33
6.46 / 6.43
6.53 / 6.52
Sound Power Level LWA
dB(A)
94
94
95
Air flow rate
m³/h
301592
324791
347991
Off mode P
OFF
kW
0.169
0.169
0.169
Thermostat-off mode P
TO
kW
3.144
3.383
3.669
Standby Mode P
SB
kW
0.343
0.348
0.353
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
241
Chiller Technical Manual 7267818 V1.13.0_01_2018