DeltaChill™ Air Cooled and FreeCool
206
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
ELECTRICAL DATA
158
159
160
Unit Data
DCC070TX-14GPYY
DCC055DX-15DYV0
DCC059DX-16DVV0
Nominal Run Amps
(1)
A
481.7
384.7
413.0
Maximum Start Amps
A
745.1
652.1
680.4
Recommended Mains Fuse Size
A
500
450
450
Evaporator
Immersion Heater Rating
W
250
170
170
Condenser Fan - Per Fan (EC)
Quantity
14
15
16
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 47.9 / 47.9
47.9 / 55.2
55.2 / 55.2
Quantity
2 + 3 + 3
3 + 3
3 + 3
Motor Rating
kW
36.2 / 29.8 / 29.8
29.8 / 33.1
33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 326 / 326
326 / 326
326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
458.0
362.8
384.0
Reactive power reduction/saving
(4)
kVAr
44.1
39.8
51.1
Maximum Start Amps
A
721.4
630.2
651.4
Recommended Mains Fuse Size
A
500
450
450
Electronic Soft-start
Nominal Run Amps
A
481.7
384.7
413.0
Maximum Start Amps
A
614.7
521.7
550.0
Recommended Mains Fuse
A
500
450
450
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
458.0
362.8
384.0
Maximum Start Amps
A
591.0
499.8
521.0
Recommended Mains Fuse Size
A
500
450
450
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
11.2
8.9
11.2
Unit Nominal Run Amps
A
492.7
393.1
424.1
Recommended Mains Fuse Size
A
560
450
450
Motor Rating
kW
6.2
4.4
6.2
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
11.2
11.2
Unit Nominal Run Amps
A
502.6
395.7
424.1
Recommended Mains Fuse Size
A
560
450
450
Motor Rating
kW
12.1
6.1
6.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.2
7.3
10.2
Unit Nominal Run Amps
A
490.0
390.5
421.2
Recommended Mains Fuse Size
A
560
450
450
Motor Rating
kW
6.4
4.5
6.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
10.1
10.1
Unit Nominal Run Amps
A
497.9
392.8
421.1
Recommended Mains Fuse Size
A
560
450
450
Motor Rating
kW
12.4
6.3
6.3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Extra Quiet