DeltaChill™ Air Cooled and FreeCool
117
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
ELECTRICAL DATA
34
35
36
Unit Data
DCF085TR-16HYYV
DCF090TR-15HVVV
DCF092TR-15HVVW
Nominal Run Amps
(1)
A
539.7
584.9
597.0
Maximum Start Amps
A
807.1
852.3
860.4
Recommended Mains Fuse Size
A
560
630
630
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
16
15
15
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.9 / 47.9 / 55.2
55.2 / 55.2 / 55.2
55.2 / 55.2 / 59.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
29.8 / 29.8 / 33.1
33.1 / 33.1 / 33.1
33.1 / 33.1 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326 / 326
326 / 326 / 326
326 / 326 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
510.3
541.0
554.7
Reactive power reduction/saving
(4) kVAr
54.0
76.4
74.3
Maximum Start Amps
A
777.7
808.4
818.1
Recommended Mains Fuse Size
A
560
630
630
Electronic Soft-start
Nominal Run Amps
A
539.7
584.9
597.0
Maximum Start Amps
A
676.7
721.9
730.0
Recommended Mains Fuse
A
560
630
630
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
510.3
541.0
554.7
Maximum Start Amps
A
647.3
678.0
687.7
Recommended Mains Fuse Size
A
560.0
630.0
630.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
568.0
613.3
625.4
Recommended Mains Fuse Size
A
630
630
670
Motor Rating
kW
16.4
16.4
16.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
35.0
Unit Nominal Run Amps
A
574.5
619.8
631.9
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
20.3
20.3
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
561.6
606.3
618.5
Recommended Mains Fuse Size
A
630
630
670
Motor Rating
kW
16.8
16.8
16.8
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
33.2
Unit Nominal Run Amps
A
566.7
611.4
623.5
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
20.7
20.7
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet