Technical Data
Ecodesign
DCC070TR-16GPPY, DCC074TR-17GPYY, DCC079TR-18GYYY
Notes: Units DCC070TR-16GPPY DCC074TR-17GPYY DCC079TR-18GYYY
SEPR
1,3,5
5.62
5.60
5.62
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
902454
956222
1026870
Rated Refrigerant Capacity
P
A
1,3,5 kW
685
722.8
778.8
Rated Power Input D
A
kW
226.1
241.7
260.5
Rated EER
DC,A
3.03
2.99
2.99
Declared Refrigerant Capacity P
B
1,3,5 kW
669.4 / 575.2
710.4 / 619.6
771.9 / 679.2
Declared Power Input D
B
kW
160.6 / 136.9
173.4 / 147.6
189.0 / 163.1
Declared EER
DC,B
4.17 / 4.20
4.10 / 4.20
4.08 / 4.16
Declared Refrigerant Capacity P
C
1,3,5 kW
621.3 / 496.0
667.6 / 567.0
732.8 / 633.1
Declared Power Input D
C
kW
114.5 / 88.9
122.9 / 103.1
136.1 / 114.2
Declared EER
DC,C
5.43 / 5.58
5.43 / 5.50
5.38 / 5.55
Declared Refrigerant Capacity P
D
1,3,5 kW
654.3 / 516.8
590.9 / 484.3
658.1 / 547.9
Declared Power Input D
D
kW
99.0 / 78.3
89.9 / 73.8
99.4 / 83.1
Declared EER
DC,D
6.61 / 6.60
6.57 / 6.56
6.62 / 6.59
SSCEE
2,3,5
%
169.1
172.4
172.6
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
688.1
724.9
781.6
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
685
722.8
778.8
Declared EER
d
35°C
3.03
2.99
2.99
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
669.4 / 575.2
710.4 / 619.6
771.9 / 679.2
Declared EER
d
30°C
4.17 / 4.20
4.10 / 4.20
4.08 / 4.16
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
621.3 / 496.0
667.6 / 567.0
732.8 / 633.1
Declared EER
d
25°C
5.43 / 5.58
5.43 / 5.50
5.38 / 5.55
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
654.3 / 516.8
590.9 / 484.3
658.1 / 547.9
Declared EER
d
20°C
6.61 / 6.60
6.57 / 6.56
6.62 / 6.59
Sound Power Level LWA
dB(A)
93
93
93
Air flow rate
m³/h
371190
394390
417589
Off mode P
OFF
kW
0.169
0.169
0.169
Thermostat-off mode P
TO
kW
3.809
2.552
3.315
Standby Mode P
SB
kW
0.335
0.351
0.368
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
250
Chiller Technical Manual 7267818 V1.13.0_01_2018