Technical Data
Ecodesign
DCC059DX-16DVV0, DCC061DX-16DVW0, DCC065DX-16DWW0
Notes: Units DCC059DX-16DVV0 DCC061DX-16DVW0 DCC065DX-16DWW0
SEPR
1,3,5
5.89
5.81
5.72
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
715158
757802
815397
Rated Refrigerant Capacity
P
A
1,3,5 kW
568.1
594.1
629.1
Rated Power Input D
A
kW
178.1
191.0
206.3
Rated EER
DC,A
3.19
3.11
3.05
Declared Refrigerant Capacity P
B
1,3,5 kW
532.4 / 429.1
664.8 / 553.0
592.7 / 479.4
Declared Power Input D
B
kW
120.5 / 94.5
157.0 / 127.0
139.6 / 109.5
Declared EER
DC,B
4.42 / 4.54
4.23 / 4.35
4.24 / 4.38
Declared Refrigerant Capacity P
C
1,3,5 kW
574.1 / 463.4
595.5 / 485.5
641.2 / 517.9
Declared Power Input D
C
kW
100.4 / 78.6
105.6 / 83.9
116.8 / 91.3
Declared EER
DC,C
5.72 / 5.89
5.64 / 5.79
5.49 / 5.68
Declared Refrigerant Capacity P
D
1,3,5 kW
475.7 / 356.1
499.0 / 367.2
534.9 / 400.3
Declared Power Input D
D
kW
70.6 / 53.5
74.7 / 55.4
80.6 / 61.2
Declared EER
DC,D
6.74 / 6.66
6.68 / 6.63
6.64 / 6.54
SSCEE
2,3,5
%
179.5
179.3
171.7
SSCEE Tier
6
Tier 2 (2021)
Tier 2 (2021)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
570.6
596.3
632.5
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
568.1
594.1
629.1
Declared EER
d
35°C
3.19
3.11
3.05
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
532.4 / 429.1
664.8 / 553.0
592.7 / 479.4
Declared EER
d
30°C
4.42 / 4.54
4.23 / 4.35
4.24 / 4.38
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
574.1 / 463.4
595.5 / 485.5
641.2 / 517.9
Declared EER
d
25°C
5.72 / 5.89
5.64 / 5.79
5.49 / 5.68
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
475.7 / 356.1
499.0 / 367.2
534.9 / 400.3
Declared EER
d
20°C
6.74 / 6.66
6.68 / 6.63
6.64 / 6.54
Sound Power Level LWA
dB(A)
88
89
89
Air flow rate
m³/h
254286
254286
254286
Off mode P
OFF
kW
0.157
0.157
0.157
Thermostat-off mode P
TO
kW
2.950
2.701
4.047
Standby Mode P
SB
kW
0.311
0.311
0.311
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
264
Chiller Technical Manual 7267818 V1.13.0_01_2018