Technical Data
Ecodesign
DCC050DR-12EPV0, DCC052DR-12EYY0, DCC056DR-13DYV0
Notes: Units DCC050DR-12EPV0 DCC052DR-12EYY0 DCC056DR-13DYV0
SEPR
1,3,5
5.62
5.47
5.70
SEPR Tier
Tier 2 (2021)
Tier 1 (2018)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
643239
690785
703938
Rated Refrigerant Capacity
P
A
1,3,5 kW
487.5
509.6
541.5
Rated Power Input D
A
kW
160.4
173.3
177.5
Rated EER
DC,A
3.04
2.94
3.05
Declared Refrigerant Capacity P
B
1,3,5 kW
539.9 / 442.0
563.9 / 472.9
600.2 / 499.7
Declared Power Input D
B
kW
131.4 / 104.9
143.0 / 117.2
145.9 / 119.2
Declared EER
DC,B
4.11 / 4.21
3.94 / 4.04
4.11 / 4.19
Declared Refrigerant Capacity P
C
1,3,5 kW
475.9 / 368.3
508.0 / 410.5
538.1 / 438.1
Declared Power Input D
C
kW
87.3 / 67.0
97.7 / 75.9
99.3 / 77.4
Declared EER
DC,C
5.45 / 5.50
5.20 / 5.41
5.42 / 5.66
Declared Refrigerant Capacity P
D
1,3,5 kW
497.3 / 384.6
424.6 / 317.9
453.3 / 336.2
Declared Power Input D
D
kW
75.7 / 58.8
66.3 / 50.1
67.9 / 50.8
Declared EER
DC,D
6.57 / 6.54
6.41 / 6.34
6.68 / 6.62
SSCEE
2,3,5
%
17%.6
167.9
176.6
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
489.5
511.8
543.1
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
487.5
509.6
541.5
Declared EER
d
35°C
3.04
2.94
3.05
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
539.9 / 442.0
563.9 / 472.9
600.2 / 499.7
Declared EER
d
30°C
4.11 / 4.21
3.94 / 4.04
4.11 / 4.19
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
475.9 / 368.3
508.0 / 410.5
538.1 / 438.1
Declared EER
d
25°C
5.45 / 5.50
5.20 / 5.41
5.42 / 5.66
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
497.3 / 384.6
424.6 / 317.9
453.3 / 336.2
Declared EER
d
20°C
6.57 / 6.54
6.41 / 6.34
6.68 / 6.62
Sound Power Level LWA
dB(A)
91
91
91
Air flow rate
m³/h
278393
278393
301592
Off mode P
OFF
kW
0.157
0.157
0.157
Thermostat-off mode P
TO
kW
2.312
2.574
2.008
Standby Mode P
SB
kW
0.279
0.291
0.296
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
248
Chiller Technical Manual 7267818 V1.13.0_01_2018