Technical Data
Ecodesign
DCC077TX-16GYYV, DCC080TX-17GYVV, DCC083TX-18GVVV
Notes: Units DCC077TX-16GYYV DCC080TX-17GYVV DCC083TX-18GVVV
SEPR
1,3,5
5.50
5.56
5.61
SEPR Tier
Tier 1 (2018)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1020572
1039649
1058596
Rated Refrigerant Capacity
P
A
1,3,5 kW
757.4
779.7
801.7
Rated Power Input D
A
kW
273.4
276.5
279.3
Rated EER
DC,A
2.77
2.82
2.87
Declared Refrigerant Capacity P
B
1,3,5 kW
762.7 / 678.4
787.0 / 692.8
811.0 / 716.8
Declared Power Input D
B
kW
197.3 / 170.0
199.1 / 171.6
201.3 / 173.8
Declared EER
DC,B
3.87 / 3.99
3.95 / 4.04
4.03 / 4.13
Declared Refrigerant Capacity P
C
1,3,5 kW
736.8 / 641.1
752.3 / 656.5
777.1 / 671.7
Declared Power Input D
C
kW
141.9 / 119.0
143.0 / 120.1
144.9 / 121.6
Declared EER
DC,C
5.19 / 5.39
5.26 / 5.47
5.36 / 5.53
Declared Refrigerant Capacity P
D
1,3,5 kW
671.5 / 554.6
685.3 / 568.3
698.7 / 581.8
Declared Power Input D
D
kW
102.2 / 84.9
103.7 / 86.4
105.5 / 88.3
Declared EER
DC,D
6.57 / 6.53
6.61 / 6.58
6.62 / 6.59
SSCEE
2,3,5
%
167.1
169.8
171.6
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
760.2
782.4
804.7
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
757.4
779.7
801.7
Declared EER
d
35°C
2.77
2.82
2.87
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
762.7 / 678.4
787.0 / 692.8
811.0 / 716.8
Declared EER
d
30°C
3.87 / 3.99
3.95 / 4.04
4.03 / 4.13
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
736.8 / 641.1
752.3 / 656.5
777.1 / 671.7
Declared EER
d
25°C
5.19 / 5.39
5.26 / 5.47
5.36 / 5.53
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
671.5 / 554.6
685.3 / 568.3
698.7 / 581.8
Declared EER
d
20°C
6.57 / 6.53
6.61 / 6.58
6.62 / 6.59
Sound Power Level LWA
dB(A)
89
89
90
Air flow rate
m³/h
254286
270179
286072
Off mode P
OFF
kW
0.169
0.169
0.169
Thermostat-off mode P
TO
kW
3.847
3.324
3.555
Standby Mode P
SB
kW
0.358
0.363
0.368
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
256
Chiller Technical Manual 7267818 V1.13.0_01_2018