Technical Data
Ecodesign
DCC080TX-19GYYV, DCC082TX-20GYVV, DCC085TX-21GVVV
Notes: Units DCC080TX-19GYYV DCC082TX-20GYVV DCC085TX-21GVVV
SEPR
1,3,5
5.66
5.69
5.72
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1023586
1045105
1064742
Rated Refrigerant Capacity
P
A
1,3,5 kW
781.6
802.1
822.6
Rated Power Input D
A
kW
263.2
267.4
271.5
Rated EER
DC,A
2.97
3
3.03
Declared Refrigerant Capacity P
B
1,3,5 kW
779.8 / 689.9
802.3 / 703.6
824.7 / 726.0
Declared Power Input D
B
kW
190.4 / 164.7
193.2 / 166.8
196.1 / 169.6
Declared EER
DC,B
4.10 / 4.19
4.15 / 4.22
4.20 / 4.28
Declared Refrigerant Capacity P
C
1,3,5 kW
747.5 / 647.9
762.2 / 662.5
784.6 / 677.2
Declared Power Input D
C
kW
137.6 / 115.7
139.2 / 117.3
141.4 / 119.0
Declared EER
DC,C
5.43 / 5.60
5.48 / 5.65
5.55 / 5.69
Declared Refrigerant Capacity P
D
1,3,5 kW
671.7 / 554.7
685.1 / 568.2
698.6 / 581.6
Declared Power Input D
D
kW
101.2 / 84.1
103.2 / 86.1
105.2 / 88.1
Declared EER
DC,D
6.64 / 6.59
6.64 / 6.60
6.64 / 6.60
SSCEE
2,3,5
%
173.3
173.9
175.1
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
784.3
805
825.7
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
781.6
802.1
822.6
Declared EER
d
35°C
2.97
3
3.03
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
779.8 / 689.9
802.3 / 703.6
824.7 / 726.0
Declared EER
d
30°C
4.10 / 4.19
4.15 / 4.22
4.20 / 4.28
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
747.5 / 647.9
762.2 / 662.5
784.6 / 677.2
Declared EER
d
25°C
5.43 / 5.60
5.48 / 5.65
5.55 / 5.69
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
671.7 / 554.7
685.1 / 568.2
698.6 / 581.6
Declared EER
d
20°C
6.64 / 6.59
6.64 / 6.60
6.64 / 6.60
Sound Power Level LWA
dB(A)
89
89
90
Air flow rate
m³/h
301965
317858
333751
Off mode P
OFF
kW
0.169
0.169
0.169
Thermostat-off mode P
TO
kW
3.369
3.588
3.845
Standby Mode P
SB
kW
0.373
0.378
0.383
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections