l
Chillers
DeltaChill™ Air Cooled and FreeCool
196
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
128
129
130
Unit Data
DCC088TR-15GVWW
DCC091TR-15GWWW
DCC074TR-17GPYY
Nominal Run Amps
(1)
A
609.1
621.2
493.3
Maximum Start Amps
A
872.5
856.6
756.7
Recommended Mains Fuse Size
A
630
670
560
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
15
15
17
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 59.2 / 59.2
59.2 / 59.2 / 59.2
59.2 / 47.9 / 47.9
Quantity
3 + 3 + 3
3 + 3 + 3
2 + 3 + 3
Motor Rating
kW
33.1 / 36.2 / 36.2
36.2 / 36.2 / 36.2
36.2 / 29.8 / 29.8
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 298 / 298
298 / 298 / 298
298 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
568.4
582.1
469.7
Reactive power reduction/saving
(4)
kVAr
72.3
70.2
44.2
Maximum Start Amps
A
831.8
817.5
733.1
Recommended Mains Fuse Size
A
630
670
560
Electronic Soft-start
Nominal Run Amps
A
609.1
621.2
493.3
Maximum Start Amps
A
742.1
737.4
626.3
Recommended Mains Fuse
A
630
670
560
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
568.4
582.1
469.7
Maximum Start Amps
A
701.4
698.3
602.7
Recommended Mains Fuse Size
A
630
670
560
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
11.2
15.2
11.2
Unit Nominal Run Amps
A
620.1
636.2
504.3
Recommended Mains Fuse Size
A
670
670
560
Motor Rating
kW
6.2
8.4
6.2
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
630.1
642.2
514.3
Recommended Mains Fuse Size
A
670
670
560
Motor Rating
kW
12.1
12.1
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.2
13.9
10.2
Unit Nominal Run Amps
A
617.2
632.3
501.6
Recommended Mains Fuse Size
A
670
670
560
Motor Rating
kW
6.4
8.6
6.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
625.0
637.2
509.5
Recommended Mains Fuse Size
A
670
670
560
Motor Rating
kW
12.4
12.4
12.4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Regular Quiet