Te
ch
ni
ca
l
Chillers
DeltaChill™ Air Cooled and FreeCool
200
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
140
141
142
Unit Data
DCC090TR-21GVVW
DCC093TR-21GVWW
DCC096TR-21GWWW
Nominal Run Amps
(1)
A
620.1
632.2
644.4
Maximum Start Amps
A
883.5
895.6
879.8
Recommended Mains Fuse Size
A
670
670
670
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
21
21
21
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2 / 59.2
55.2 / 59.2 / 59.2
59.2 / 59.2 / 59.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
33.1 / 33.1 / 36.2
33.1 / 36.2 / 36.2
36.2 / 36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326 / 298
326 / 298 / 298
298 / 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
578.0
591.7
605.4
Reactive power reduction/saving
(4)
kVAr
74.5
72.4
70.3
Maximum Start Amps
A
841.4
855.1
840.8
Recommended Mains Fuse Size
A
670
670
670
Electronic Soft-start
Nominal Run Amps
A
620.1
632.2
644.4
Maximum Start Amps
A
753.1
765.2
760.6
Recommended Mains Fuse
A
670
670
670
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
578.0
591.7
605.4
Maximum Start Amps
A
711.0
724.7
721.6
Recommended Mains Fuse Size
A
670
670
670
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
15.2
15.2
15.2
Unit Nominal Run Amps
A
635.1
647.2
659.3
Recommended Mains Fuse Size
A
670
670
710
Motor Rating
kW
8.4
8.4
8.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
641.1
653.2
665.4
Recommended Mains Fuse Size
A
670
710
710
Motor Rating
kW
12.1
12.1
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
13.9
13.9
13.9
Unit Nominal Run Amps
A
631.2
643.3
655.5
Recommended Mains Fuse Size
A
670
670
710
Motor Rating
kW
8.6
8.6
8.6
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
636.0
648.1
660.3
Recommended Mains Fuse Size
A
670
670
710
Motor Rating
kW
12.4
12.4
12.4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Regular Quiet