Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
147
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
Ambient (°C)
Model
Supply
Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
124
DCC077TR-15GYYY
5
806.1
216.5
769.0
238.6
726.8
263.7
680.6
291.7
6
830.3
218.1
792.3
240.3
749.0
265.4
701.0
293.1
7
855.6
219.9
815.9
241.9
771.6
267.0
721.7
294.5
8
879.9
221.5
839.9
243.6
794.6
268.8
742.7
295.9
9
905.1
223.2
864.3
245.4
818.0
270.5
764.0
297.4
10
930.7
224.9
889.0
247.1
841.7
272.3
785.6
298.9
125
DCC080TR-16GYYV
5
826.9
218.8
788.2
241.3
745.0
267.1
697.4
295.9
6
851.8
220.4
812.6
243.0
767.9
268.7
718.7
297.4
7
877.5
222.2
836.9
244.7
791.2
270.4
740.2
298.9
8
902.6
223.7
861.3
246.3
814.8
272.1
762.1
300.4
9
928.5
225.4
886.3
248.0
838.8
273.8
784.4
301.9
10
954.7
227.2
911.7
249.8
863.2
275.6
807.0
303.5
126
DCC083TR-15GVVV
5
856.2
231.7
816.4
256.0
770.9
283.7
716.3
313.2
6
882.0
233.4
841.3
257.7
794.0
285.2
737.8
314.6
7
908.2
235.2
866.6
259.5
817.3
286.7
759.7
316.2
8
934.7
237.0
892.2
261.3
840.9
288.3
781.9
317.7
9
961.4
238.8
918.1
263.2
864.9
289.9
804.4
319.3
10
988.5
240.7
944.4
265.1
889.1
291.5
827.3
321.0
127
DCC086TR-15GVVW
5
897.0
244.9
853.8
270.0
803.5
298.3
745.7
329.1
6
924.1
246.8
879.5
271.8
827.3
300.0
767.9
330.7
7
951.5
248.8
905.6
273.7
851.5
301.7
790.5
332.5
8
979.4
250.7
932.1
275.6
876.1
303.4
813.5
334.2
9
1007.6
252.7
958.9
277.6
900.9
305.2
836.8
336.0
10
1036.0
254.8
986.1
279.6
926.1
307.1
860.4
337.8
128
DCC088TR-15GVWW
5
929.0
257.5
883.7
283.5
830.0
312.5
770.2
344.7
6
956.8
259.5
909.7
285.3
854.3
314.3
792.8
346.5
7
984.9
261.6
936.1
287.2
878.9
316.2
815.8
348.4
8
1013.3
263.7
962.7
289.2
903.8
318.1
839.1
350.3
9
1042.2
265.8
989.7
291.2
929.1
320.0
862.8
352.2
10
1070.9
267.9
1017.0
293.3
954.6
322.0
886.8
354.2
129
DCC091TR-15GWWW
5
961.1
270.1
913.6
296.9
856.5
326.7
794.7
360.3
6
989.5
272.2
939.9
298.8
881.2
328.7
817.7
362.2
7
1018.2
274.4
966.5
300.8
906.2
330.7
841.1
364.3
8
1047.3
276.6
993.4
302.8
931.6
332.8
864.8
366.3
9
1076.7
278.8
1020.5
304.8
957.2
334.9
888.8
368.4
10
1105.9
281.0
1048.0
306.9
983.1
337.0
913.2
370.6
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (comp fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.
DCC Performance Data EC Fans