Notes: Units DCF094TX-18HVWW DCF096TX-18HWWW DCF049DX-11DXY0
SEPR
1,3,5
6.27
6.17
6.63
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1019004
1060559
504351
Rated Refrigerant Capacity
P
A
1,3,5 kW
862.5
883.1
451.4
Rated Power Input D
A
kW
321.8
337.1
156.2
Rated EER
DC,A
2.68
2.62
2.89
Declared Refrigerant Capacity P
B
1,3,5 kW
880.9 / 779.7
905.6 / 805.1
422.1 / 351.2
Declared Power Input D
B
kW
230.7 / 196.5
242.7 / 208.6
102.7 / 83.0
Declared EER
DC,B
3.82 / 3.97
3.73 / 3.86
4.11 / 4.23
Declared Refrigerant Capacity P
C
1,3,5 kW
850.2 / 743.1
878.8 / 763.9
461.2 / 381.9
Declared Power Input D
C
kW
164.5 / 140.4
174.1 / 145.8
86.2 / 69.2
Declared EER
DC,C
5.17 / 5.29
5.05 / 5.24
5.35 / 5.51
Declared Refrigerant Capacity P
D
1,3,5 kW
684.6 / 646.9
701.7 / 670.6
358.5 / 287.7
Declared Power Input D
D
kW
73.0 / 99.2
76.3 / 103.3
35.3 / 43.1
Declared EER
DC,D
9.37 / 6.52
9.20 / 6.49
10.16 / 6.68
SSCEE
2,3,5
%
159.8
159.8
167.6
SSCEE Tier
6
Not Compliant
Not Compliant
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
n/a
n/a
454.1
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
n/a
n/a
451.4
Declared EER
d
35°C
n/a
n/a
2.89
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
n/a
n/a
422.1 / 351.2
Declared EER
d
30°C
n/a
n/a
4.11 / 4.23
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
n/a
n/a
461.2 / 381.9
Declared EER
d
25°C
n/a
n/a
5.35 / 5.51
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
n/a
n/a
358.5 / 287.7
Declared EER
d
20°C
n/a
n/a
10.16 / 6.68
Sound Power Level LWA
dB(A)
n/a
n/a
Air flow rate
m³/h
n/a
n/a
158303
Off mode P
OFF
kW
n/a
n/a
0.157
Thermostat-off mode P
TO
kW
n/a
n/a
3.026
Standby Mode P
SB
kW
n/a
n/a
0.286
Crankcase heater mode P
CK
kW
n/a
n/a
0.000
Technical Data
Ecodesign
DCF098TR-21HVVW, DCF101TR-21HVWW, DCF103TR-21HWWW
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
289