Notes: Units DCF085TX-17HYVV DCF089TX-18HVVV DCF092TX-18HVVW
SEPR
1,3,5
6.20
6.42
6.38
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
928723
936291
971522
Rated Refrigerant Capacity
P
A
1,3,5 kW
777.4
811.2
837.2
Rated Power Input D
A
kW
285.8
290.8
305.5
Rated EER
DC,A
2.72
2.79
2.74
Declared Refrigerant Capacity P
B
1,3,5 kW
789.2 / 695.9
827.7 / 733.4
851.2 / 756.9
Declared Power Input D
B
kW
206.6 / 178.1
210.1 / 181.4
217.2 / 188.6
Declared EER
DC,B
3.82 / 3.91
3.94 / 4.04
3.92 / 4.01
Declared Refrigerant Capacity P
C
1,3,5 kW
758.2 / 663.1
799.7 / 692.5
825.3 / 718.2
Declared Power Input D
C
kW
148.7 / 125.0
151.7 / 127.6
157.7 / 133.6
Declared EER
DC,C
5.10 / 5.31
5.27 / 5.43
5.23 / 5.38
Declared Refrigerant Capacity P
D
1,3,5 kW
617.1 / 576.4
643.6 / 605.2
664.7 / 619.5
Declared Power Input D
D
kW
67.3 / 89.5
67.1 / 92.1
69.3 / 94.0
Declared EER
DC,D
9.17 / 6.44
9.59 / 6.57
9.60 / 6.59
SSCEE
2,3,5
%
159.0
161.9
162.5
SSCEE Tier
6
Not Compliant
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
n/a
816.6
842.2
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
n/a
811.2
837.2
Declared EER
d
35°C
n/a
2.79
2.74
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
n/a
827.7 / 733.4
851.2 / 756.9
Declared EER
d
30°C
n/a
3.94 / 4.04
3.92 / 4.01
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
n/a
799.7 / 692.5
825.3 / 718.2
Declared EER
d
25°C
n/a
5.27 / 5.43
5.23 / 5.38
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
n/a
643.6 / 605.2
664.7 / 619.5
Declared EER
d
20°C
n/a
9.59 / 6.57
9.60 / 6.59
Sound Power Level LWA
dB(A)
n/a
Air flow rate
m³/h
n/a
259041
259041
Off mode P
OFF
kW
n/a
0.169
0.169
Thermostat-off mode P
TO
kW
n/a
6.198
5.842
Standby Mode P
SB
kW
n/a
0.368
0.368
Crankcase heater mode P
CK
kW
n/a
0.000
0.000
Technical Data
Ecodesign
DCF085TX-17HYVV
,
DCF089TX-18HVVV
,
DCF092TX-18HVVW
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.