Chillers
DeltaChill™ Air Cooled and FreeCool
120
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
ni
ca
l
Fr
ee
C
oo
l
ELECTRICAL DATA
43
44
45
Unit Data
DCF095TR-18HVVW
DCF098TR-18HVWW
DCF100TR-18HWWW
Nominal Run Amps
(1)
A
608.5
620.6
632.8
Maximum Start Amps
A
871.9
884.0
868.2
Recommended Mains Fuse Size
A
630
670
670
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
18
18
18
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2 / 59.2
55.2 / 59.2 / 59.2
59.2 / 59.2 / 59.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
33.1 / 33.1 / 36.2
33.1 / 36.2 / 36.2
36.2 / 36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326 / 298
326 / 298 / 298
298 / 298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
566.4
580.1
593.7
Reactive power reduction/saving
(4) kVAr
74.4
72.3
70.3
Maximum Start Amps
A
829.8
843.5
829.1
Recommended Mains Fuse Size
A
630
670
670
Electronic Soft-start
Nominal Run Amps
A
608.5
620.6
632.8
Maximum Start Amps
A
741.5
753.6
749.0
Recommended Mains Fuse
A
630
670
670
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
566.4
580.1
593.7
Maximum Start Amps
A
699.4
713.1
709.9
Recommended Mains Fuse Size
A
630.0
670.0
670.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
35.0
Unit Nominal Run Amps
A
636.9
649.0
667.6
Recommended Mains Fuse Size
A
670
670
710
Motor Rating
kW
16.4
16.4
20.3
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
41.5
Unit Nominal Run Amps
A
643.4
655.5
674.0
Recommended Mains Fuse Size
A
670
710
710
Motor Rating
kW
20.3
20.3
23.9
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
33.2
Unit Nominal Run Amps
A
630.1
642.2
659.5
Recommended Mains Fuse Size
A
670
670
710
Motor Rating
kW
16.8
16.8
20.7
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
39.2
Unit Nominal Run Amps
A
635.1
647.3
664.4
Recommended Mains Fuse Size
A
670
710
710
Motor Rating
kW
20.7
20.7
24.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet