Chillers
DeltaChill™ Air Cooled and FreeCool
118
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
ni
ca
l
Fr
ee
C
oo
l
ELECTRICAL DATA
37
38
39
Unit Data
DCF094TR-15HVWW
DCF096TR-15HWWW
DCF080TR-17GPYY
Nominal Run Amps
(1)
A
609.1
621.2
493.3
Maximum Start Amps
A
872.5
856.6
756.7
Recommended Mains Fuse Size
A
630
670
560
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
15
15
17
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 59.2 / 59.2
59.2 / 59.2 / 59.2
59.2 / 47.9 / 47.9
Quantity
3 + 3 + 3
3 + 3 + 3
2 + 3 + 3
Motor Rating
kW
33.1 / 36.2 / 36.2
36.2 / 36.2 / 36.2
36.2 / 29.8 / 29.8
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 298 / 298
298 / 298 / 298
298 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
568.4
582.1
469.7
Reactive power reduction/saving
(4) kVAr
72.3
70.2
44.2
Maximum Start Amps
A
831.8
817.5
733.1
Recommended Mains Fuse Size
A
630
670
560
Electronic Soft-start
Nominal Run Amps
A
609.1
621.2
493.3
Maximum Start Amps
A
742.1
737.4
626.3
Recommended Mains Fuse
A
630
670
560
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
568.4
582.1
469.7
Maximum Start Amps
A
701.4
698.3
602.7
Recommended Mains Fuse Size
A
630.0
670.0
560.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
35.0
28.5
Unit Nominal Run Amps
A
637.4
656.0
521.5
Recommended Mains Fuse Size
A
670
710
560
Motor Rating
kW
16.4
20.3
16.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
35.0
41.5
35.0
Unit Nominal Run Amps
A
643.9
662.4
528.0
Recommended Mains Fuse Size
A
670
710
560
Motor Rating
kW
20.3
23.9
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
33.2
26.9
Unit Nominal Run Amps
A
630.6
647.9
515.3
Recommended Mains Fuse Size
A
670
710
560
Motor Rating
kW
16.8
20.7
16.8
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
33.2
39.2
33.2
Unit Nominal Run Amps
A
635.7
652.8
520.5
Recommended Mains Fuse Size
A
670
710
560
Motor Rating
kW
20.7
24.4
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet