Notes: Units DCF061DX-16DVV0 DCF066DX-16FVW0 DCF069DX-16FWW0
SEPR
1,3,5
6.72
6.72
6.62
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
618005
662441
705943
Rated Refrigerant Capacity
P
A
1,3,5 kW
560.5
601.2
630.7
Rated Power Input D
A
kW
181.4
197.1
211.6
Rated EER
DC,A
3.09
3.05
2.98
Declared Refrigerant Capacity P
B
1,3,5 kW
528.1 / 426.3
565.3 / 461.5
599.2 / 486.3
Declared Power Input D
B
kW
123.1 / 96.6
131.8 / 105.1
143.5 / 112.5
Declared EER
DC,B
4.29 / 4.41
4.29 / 4.39
4.17 / 4.32
Declared Refrigerant Capacity P
C
1,3,5 kW
572.4 / 462.2
614.4 / 501.5
653.4 / 528.2
Declared Power Input D
C
kW
102.6 / 80.3
110.2 / 87.7
120.3 / 94.0
Declared EER
DC,C
5.58 / 5.75
5.57 / 5.72
5.43 / 5.62
Declared Refrigerant Capacity P
D
1,3,5 kW
445.5 / 356.6
477.4 / 381.8
500.8 / 411.2
Declared Power Input D
D
kW
45.5 / 54.1
48.3 / 57.4
51.1 / 62.2
Declared EER
DC,D
9.80 / 6.59
9.87 / 6.65
9.79 / 6.61
SSCEE
2,3,5
%
173.8
171.7
168.7
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
563.3
604.8
634.6
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
560.5
601.2
630.7
Declared EER
d
35°C
3.09
3.05
2.98
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
528.1 / 426.3
565.3 / 461.5
599.2 / 486.3
Declared EER
d
30°C
4.29 / 4.41
4.29 / 4.39
4.17 / 4.32
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
572.4 / 462.2
614.4 / 501.5
653.4 / 528.2
Declared EER
d
25°C
5.58 / 5.75
5.57 / 5.72
5.43 / 5.62
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
445.5 / 356.6
477.4 / 381.8
500.8 / 411.2
Declared EER
d
20°C
9.80 / 6.59
9.87 / 6.65
9.79 / 6.61
Sound Power Level LWA
dB(A)
Air flow rate
m³/h
230259
230259
230259
Off mode P
OFF
kW
0.157
0.157
0.157
Thermostat-off mode P
TO
kW
3.372
4.244
4.344
Standby Mode P
SB
kW
0.311
0.311
0.311
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Technical Data
Ecodesign
DCF061DX-16DVV0, DCF066DX-16FVW0, DCF069DX-16FWW0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction