Technical Data
Ecodesign
DCC050DX-14EPV0, DCC052DX-14EYY0, DCC055DX-15DYV0
Notes: Units DCC050DX-14EPV0 DCC052DX-14EYY0 DCC055DX-15DYV0
SEPR
1,3,5
5.77
5.58
5.81
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
627687
677448
690738
Rated Refrigerant Capacity
P
A
1,3,5 kW
489
510.1
542
Rated Power Input D
A
kW
155.7
168.3
172.6
Rated EER
DC,A
3.14
3.03
3.14
Declared Refrigerant Capacity P
B
1,3,5 kW
545.4 / 446.3
476.8 / 384.8
605.3 / 503.5
Declared Power Input D
B
kW
128.0 / 102.3
114.3 / 89.5
142.2 / 116.3
Declared EER
DC,B
4.26 / 4.36
4.17 / 4.30
4.26 / 4.33
Declared Refrigerant Capacity P
C
1,3,5 kW
480.4 / 371.9
512.4 / 413.6
542.8 / 441.3
Declared Power Input D
C
kW
85.0 / 65.2
95.1 / 74.2
96.9 / 75.8
Declared EER
DC,C
5.65 / 5.71
5.39 / 5.57
5.60 / 5.82
Declared Refrigerant Capacity P
D
1,3,5 kW
497.3 / 384.6
424.5 / 317.8
453.2 / 336.2
Declared Power Input D
D
kW
74.8 / 57.9
66.1 / 50.0
67.7 / 50.6
Declared EER
DC,D
6.65 / 6.64
6.43 / 6.35
6.70 / 6.64
SSCEE
2,3,5
%
175.3
171.6
18%.5
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2,4,5
491
512.4
543.6
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
489
510.1
542
Declared EER
d
35°C
3.14
3.03
3.14
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
545.4 / 446.3
476.8 / 384.8
605.3 / 503.5
Declared EER
d
30°C
4.26 / 4.36
4.17 / 4.30
4.26 / 4.33
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
480.4 / 371.9
512.4 / 413.6
542.8 / 441.3
Declared EER
d
25°C
5.65 / 5.71
5.39 / 5.57
5.60 / 5.82
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
497.3 / 384.6
424.5 / 317.8
453.2 / 336.2
Declared EER
d
20°C
6.65 / 6.64
6.43 / 6.35
6.70 / 6.64
Sound Power Level LWA
dB(A)
88
86
87
Air flow rate
m³/h
222501
222501
238393
Off mode P
OFF
kW
0.157
0.157
0.157
Thermostat-off mode P
TO
kW
2.343
2.597
2.043
Standby Mode P
SB
kW
0.289
0.301
0.306
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
263