Technical Data
Ecodesign
DCC058DR-12DVV0, DCC060DR-12DVW0, DCC063DR-12DWW0
Notes: Units DCC058DR-12DVV0 DCC060DR-12DVW0 DCC063DR-12DWW0
SEPR
1,3,5
5.66
5.57
5.47
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 1 (2018)
Annual Electricity Consumption
kWh/a
734089
782645
848411
Rated Refrigerant Capacity
P
A
1,3,5 kW
560.9
588.8
626.1
Rated Power Input D
A
kW
187.6
201.6
218.2
Rated EER
DC,A
2.99
2.92
2.87
Declared Refrigerant Capacity P
B
1,3,5 kW
623.0 / 522.8
652.8 / 543.0
694.2 / 583.0
Declared Power Input D
B
kW
154.1 / 126.2
165.7 / 133.2
179.7 / 147.0
Declared EER
DC,B
4.04 / 4.14
3.94 / 4.08
3.86 / 3.97
Declared Refrigerant Capacity P
C
1,3,5 kW
564.0 / 456.3
585.0 / 477.9
628.9 / 509.3
Declared Power Input D
C
kW
105.4 / 81.9
111.1 / 87.6
123.1 / 95.5
Declared EER
DC,C
5.35 / 5.57
5.27 / 5.45
5.11 / 5.33
Declared Refrigerant Capacity P
D
1,3,5 kW
475.7 / 356.2
499.1 / 367.3
534.9 / 400.4
Declared Power Input D
D
kW
71.1 / 53.7
75.3 / 55.6
81.6 / 61.7
Declared EER
DC,D
6.69 / 6.63
6.63 / 6.61
6.56 / 6.49
SSCEE
2,3,5
%
172.3
171.8
164.3
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
563.2
590.9
629.4
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
560.9
588.8
626.1
Declared EER
d
35°C
2.99
2.92
2.87
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
623.0 / 522.8
652.8 / 543.0
694.2 / 583.0
Declared EER
d
30°C
4.04 / 4.14
3.94 / 4.08
3.86 / 3.97
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
564.0 / 456.3
585.0 / 477.9
628.9 / 509.3
Declared EER
d
25°C
5.35 / 5.57
5.27 / 5.45
5.11 / 5.33
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
475.7 / 356.2
499.1 / 367.3
534.9 / 400.4
Declared EER
d
20°C
6.69 / 6.63
6.63 / 6.61
6.56 / 6.49
Sound Power Level LWA
dB(A)
92
93
94
Air flow rate
m³/h
278393
278393
278393
Off mode P
OFF
kW
0.157
0.157
0.157
Thermostat-off mode P
TO
kW
2.807
2.581
3.930
Standby Mode P
SB
kW
0.291
0.291
0.291
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
244
Chiller Technical Manual 7267818 V1.13.0_01_2018