Notes: Units DCF051DX-11DPY0 DCF053DX-12DPV0 DCF055DX-12DYY0
SEPR
1,3,5
6.49
6.54
6.39
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
532598
552568
586079
Rated Refrigerant Capacity
P
A
1,3,5 kW
466.4
487.8
505.5
Rated Power Input D
A
kW
161.4
165.4
178.6
Rated EER
DC,A
2.89
2.95
2.83
Declared Refrigerant Capacity P
B
1,3,5 kW
438.9 / 341.7
552.3 / 453.4
482.6 / 393.7
Declared Power Input D
B
kW
107.1 / 82.6
136.6 / 109.3
121.3 / 94.8
Declared EER
DC,B
4.10 / 4.14
4.04 / 4.15
3.98 / 4.15
Declared Refrigerant Capacity P
C
1,3,5 kW
480.2 / 375.0
495.9 / 382.5
527.0 / 427.0
Declared Power Input D
C
kW
90.0 / 69.5
91.8 / 70.6
101.7 / 79.2
Declared EER
DC,C
5.33 / 5.39
5.40 / 5.42
5.18 / 5.39
Declared Refrigerant Capacity P
D
1,3,5 kW
369.8 / 253.5
386.8 / 260.7
401.3 / 334.3
Declared Power Input D
D
kW
37.7 / 38.9
39.1 / 40.1
41.9 / 51.8
Declared EER
DC,D
9.82 / 6.51
9.90 / 6.49
9.57 / 6.46
SSCEE
2,3,5
%
161.0
161.5
163.3
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
469.7
491.4
508.6
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
466.4
487.8
505.5
Declared EER
d
35°C
2.89
2.95
2.83
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
438.9 / 341.7
552.3 / 453.4
482.6 / 393.7
Declared EER
d
30°C
4.10 / 4.14
4.04 / 4.15
3.98 / 4.15
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
480.2 / 375.0
495.9 / 382.5
527.0 / 427.0
Declared EER
d
25°C
5.33 / 5.39
5.40 / 5.42
5.18 / 5.39
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
369.8 / 253.5
386.8 / 260.7
401.3 / 334.3
Declared EER
d
20°C
9.82 / 6.51
9.90 / 6.49
9.57 / 6.46
Sound Power Level LWA
dB(A)
Air flow rate
m³/h
158303
172694
172694
Off mode P
OFF
kW
0.157
0.157
0.157
Thermostat-off mode P
TO
kW
3.678
3.970
3.593
Standby Mode P
SB
kW
0.274
0.279
0.291
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Technical Data
Ecodesign
DCF051DX-11DPY0, DCF053DX-12DPV0, DCF055DX-12DYY0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
290
Chiller Technical Manual 7267818 V1.13.0_01_2018